Table 49 100V Wattage and BTU/Hour

EVA8x00

EVA6x00

EVA4x00

Enclosures

BTU/h

Watts

VA

Amps

BTU/h

Watts

VA

Amps

BTU/h

Watts

VA

Amps

EVA8x00 not supported

11855

3474

3545

35.5

8

10518

3082

3145

31.5

7

9181

2691

2746

27.5

6

7845

2299

2346

23.5

5

6508

1907

1946

19.5

6269

1837

1875

18.7

4

5171

1516

1546

15.5

4933

1446

1475

14.8

3

3835

1124

1147

11.5

3596

1054

1075

10.8

2

2498

732

747

7.5

2259

662

676

6.8

1

UPS Selection

This section provides information that can be used when selecting a UPS for use with the EVA. The
four HP UPS products listed in

Table 50 (page 141)

are available for use with the EVA and are

included in this comparison.

Table 51 (page 141)

identifies the amount of time each UPS can sustain

power under varying loads and with various UPS ERM (Extended Runtime Module) options.
The load imposed on the UPS for different disk enclosure configurations are listed in

Table 52 (page

142)

,

Table 53 (page 142)

, and

Table 54 (page 143)

.

NOTE:

The specified power requirements reflect fully loaded enclosures (14 disks) .

Table 50 HP UPS models and capacities

Capacity (in watts)

UPS Model

1340

R1500

2700

R3000

4500

R5500

12000

R12000

Table 51 UPS operating time limits

Minutes of operation

Load (percent)

With 2 ERMs

With 1 ERM

With standby battery

R1500

49

23

5

100

63

32

6

80

161

57

13

50

290

146

34

20

R3000

20

5

100

30

6.5

80

45

12

50

120

40

20

Environmental and operating specifications