Table 49 100V Wattage and BTU/Hour
EVA8x00
EVA6x00
EVA4x00
Enclosures
BTU/h
Watts
VA
Amps
BTU/h
Watts
VA
Amps
BTU/h
Watts
VA
Amps
EVA8x00 not supported
11855
3474
3545
35.5
8
10518
3082
3145
31.5
7
9181
2691
2746
27.5
6
7845
2299
2346
23.5
5
6508
1907
1946
19.5
6269
1837
1875
18.7
4
5171
1516
1546
15.5
4933
1446
1475
14.8
3
3835
1124
1147
11.5
3596
1054
1075
10.8
2
2498
732
747
7.5
2259
662
676
6.8
1
UPS Selection
This section provides information that can be used when selecting a UPS for use with the EVA. The
four HP UPS products listed in
are available for use with the EVA and are
included in this comparison.
identifies the amount of time each UPS can sustain
power under varying loads and with various UPS ERM (Extended Runtime Module) options.
The load imposed on the UPS for different disk enclosure configurations are listed in
, and
NOTE:
The specified power requirements reflect fully loaded enclosures (14 disks) .
Table 50 HP UPS models and capacities
Capacity (in watts)
UPS Model
1340
R1500
2700
R3000
4500
R5500
12000
R12000
Table 51 UPS operating time limits
Minutes of operation
Load (percent)
With 2 ERMs
With 1 ERM
With standby battery
R1500
49
23
5
100
63
32
6
80
161
57
13
50
290
146
34
20
R3000
20
5
100
30
6.5
80
45
12
50
120
40
20