Page 123

background image

0.3.en.06 UNRECOVERABLE condition—No blowers installed

NOTE:

IMPORTANT

When this condition exists there will be two error messages.
The first message will be 0.3.en.05 and will identify the first

blower

.

The second message will be 0.3.en.06 and will identify the second

blower

.

The EMU cannot detect any installed

blowers

. Shutdown is imminent! The EMU will shut down the

enclosure in seven minutes unless you correct the problem. This condition report remains active
until you correct the problem or the EMU shuts down the power supplies, whichever occurs first.
Complete the following procedure to correct this problem.
1.

Record all six characters of the condition report.

2.

Use the controller shutdown procedure to shut down the controllers.

3.

Contact your authorized service representative.

CAUTION:

An automatic shutdown and possible data corruption may result if the

blower

is

removed before a replacement is available.

Temperature conditions

The format of a temperature condition report is 0.4.en.ec, where:

0.4. is the temperature sensor element type

en. is the two-character temperature sensor element

ec is the error code

See

Table 43 (page 123)

to determine the location of each temperature sensor.

Table 43 Temperature sensor element numbering

Sensor location

Sensor

Sensor location

Sensor

Drive Bay 7

10.

Power Supply 1 Exhaust

01.

Drive Bay 8

11.

Power Supply 2 Exhaust

02.

Drive Bay 9

12.

EMU

03.

Drive Bay 10

13.

Drive Bay 1

04.

Drive Bay 11

14.

Drive Bay 2

05.

Drive Bay 12

15.

Drive Bay 3

06.

Drive Bay 13

16.

Drive Bay 4

07.

Drive Bay 14

17.

Drive Bay 5

08.

Drive Bay 6

09.

The following sections list the temperature condition reports and the default temperature thresholds.
Use HP P6000 Command View to view the temperature sensor ranges for the disk drives, EMU,
and power supplies.

0.4.en.01 NONCRITICAL condition—High temperature

This condition report indicates that an element temperature is approaching, but has not reached,
the high temperature CRITICAL threshold. Continued operation under these conditions may result
in a CRITICAL condition. This condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem.
1.

Record all six characters of the condition report.

2.

Ensure that all elements are properly installed to maintain proper air flow.