D non-standard rack specifications, Rack specifications, Internal component envelope – HP 4000.6000.8000 Enterprise Virtual Arrays User Manual
Page 138: Eia310-d standards, Eva cabinet measures and tolerances, Weights, dimensions and component cg measurements
D Non-standard rack specifications
The appendix provides information on the requirements when installing the EVA4x00/6x00/8x00
in a non-standard rack. All the requirements must be met to ensure proper operation of the storage
system.
Rack specifications
Internal component envelope
EVA component mounting brackets require space to be mounted behind the vertical mounting rails.
Room for the mounting of the brackets includes the width of the mounting rails and needed room
for any mounting hardware, such as screws, clip nuts, etc.
shows the
dimensions required for the mounting space for the EVA product line. It does not show required
space for additional HP components such as servers.
Figure 47 Mounting space dimensions
EIA310-D standards
The rack must meet the Electronic Industries Association, (EIA), Standard 310-D, Cabinets, Racks
and Associated Equipment. The standard defines rack mount spacing and component dimensions
specified in U units.
Copies of the standard are available for purchase at
.
EVA cabinet measures and tolerances
EVA component rack mount brackets are designed to fit cabinets with mounting rails set at depths
from 27.5 inches to 29.6 inches, inside rails to inside rails.
Weights, dimensions and component CG measurements
Cabinet CG dimensions are reported as measured from the inside bottom of the cabinet (Z), the
leading edge of the vertical mounting rails (Y), and the centerline of the cabinet mounting space
(X). Component CG measurements are measured from the bottom of the U space the component
is to occupy (Z), the mounting surface of the mounting flanges (Y), and the centerline of the
component (X).
lists the CG dimensions for the EVA components.
138
Non-standard rack specifications