SK 500E – Users Manual for Frequency Inverters
96
BU 0500 GB-1013
P406
Analog input 2 mode
(Analog input 2 mode)
S
0 ... 5
{ 0 }
0 = 0 – 10V limited
1 = 0 – 10V
2 = 0 – 10V monitored
3 = - 10V – 10V
4 = 0 – 10V with Error 1
5 = 0 – 10V with Error 2
This parameter is identical to P401. P402 changes to P407.
Pos : 190 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P407 – Abgleich Analogei ngang 2: 0% [SK 500. ..535E] @ 0\ mod_1327681453169_388.doc x @ 9395 @ @ 1
P407
Adjustment 2: 0%
(Analog input 2 adjustment: 0%)
S
-50.00 ... 50.00 V
{ 0.00 }
This parameter is identical to P402.
Pos : 191 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P408 – Abgleich Analogei ngang 2: 100% [SK 500. .. 535E] @ 0\ mod_1327681513432_388. doc x @ 9418 @ @ 1
P408
Adjustment 2: 100%
(Analog input 2 adjustment: 100%)
S
-50.00 ... 50.00 V
{ 10.00 }
This parameter is identical to P403.
Pos : 192 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P409 – Filter Anal ogeing ang 2 [ SK 500.. .535E] @ 0\mod_1327681572071_388.doc x @ 9441 @ @ 1
P409
Analog input filter 2
(Filter analog input 2)
S
1 ... 400 ms
{ 100 }
This parameter is identical to P404.
Pos : 193 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P410 – Mi ni malfr equenz N ebensoll werte @ 0\ mod_1327681617600_388. doc x @ 9464 @ @ 1
P410
Min. freq. a-in 1/2
(Minimum frequency a-in 1/2 (auxiliary setpoint
value))
P
-400.0 ... 400.0 Hz
{ 0.0 }
The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:
Actual frequency PID
Frequency addition
Frequency subtraction
Auxiliary setpoints via BUS
Process controller
Min. frequency above analog setpoint (potentiometer)
Pos : 194 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P411 – M axi malfrequenz N ebens ollwert e @ 0\ mod_1327940087486_388.doc x @ 9490 @ @ 1
P411
Max. freq. a-in 1/2
(Maximum frequency a-in 1/2 (auxiliary setpoint
value))
P
-400.0 ... 400.0 Hz
{ 50.0 }
The maximum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:
Actual frequency PID
Frequency addition
Frequency subtraction
Auxiliary setpoints via BUS
Process controller
Min. frequency above analog setpoint (potentiometer)
Pos : 195 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P412 – Sollwert Prozessr egler @ 0\ mod_1327940158248_388.doc x @ 9513 @ @ 1
P412
Nom. val. process ctrl.
(Nominal value process controller)
S
P
-10.0 ... 10.0 V
{ 5.0 }
Fixed specification of a setpoint for the process controller that will only occasionally be altered.
Only with P400 = 14 ... 16 (process controller). Further details can be found in Chap. 8.2