P744 configuration, P745 module version, P746 module status – NORD Drivesystems BU0500 User Manual
Page 138: P747 inverter volt. range, P748, Status canopen
SK 500E – Users Manual for Frequency Inverters
138
BU 0500 GB-1013
Pos : 375 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P744 – Ausbaust uf e @ 0\ mod_1328178135013_388.doc x @ 13451 @ @ 1
P744
Configuration
(Configuration level)
0000 ... FFFF (hex)
This parameter displays the special devices integrated in the FI. Display is in hexadecimal code
(SimpleBox, ControlBox, Bus system).
The display is in plain text when the ParameterBox is used.
SK 500E … 515E
= 0000
SK 520E
= 0101
SK 530E … 535E
= 0201
SK 540E … 545E
= 0301
Pos : 376 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P745 – Baugruppen Versi on @ 0\ mod_1328178182499_388. doc x @ 13474 @ @ 1
P745
Module version
(Module version)
-3276.8 ... 3276.8
Version status (software version) of the technology unit (SK TU3-xxx), but only when own
processor is present, i.e. not for SK TU3-CTR.
Have this data available if you have a technical query.
Pos : 377 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P746 – Baugruppen Z ust and [SK 5xxE] @ 0\ mod_1328178220422_388. doc x @ 13497 @ @ 1
P746
Module status
(Module status)
S
0000 ... FFFF (hex)
Shows the actual status (readiness, error, communication) of the technology unit (SK TU3-xxx),
but only when own processor is present, i.e. not for SK TU3-CTR.
Code details can be found in the respective BUS module manual. Different contents are shown
depending on the modules.
Pos : 378 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P747 – U mric ht erspannungsbereic h @ 0\ mod_1328178270094_388.doc x @ 13520 @ @ 1
P747
Inverter Volt. Range
(Inverter voltage range)
0 ... 2
Indicates the mains voltage range for which this device is specified.
0 = 100...120V
1 = 200...240V
2 = 380...480V
Pos : 379 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P748 – St at us C AN open @ 0\mod_1328178317375_388. doc x @ 13543 @ @ 1
P748
[-01]
...
[-03]
Status CANopen
(CANopen status)
SK 520E or
higher
S
0000 ... FFFF (hex) [01] = CANbus/CANopen status
[-02] = reserved
[-03] = reserved
Bit 0 = 24V bus voltage supply
Bit 1 = CANbus in "Bus Warning" status
Bit 2 = CANbus in "Bus Off" status
Bit 3 ... Bit 5 = free
Bit 6 = Protocol of the CAN module is 0 =
CAN or 1 = CANopen
Bit 7 = free
Bit 8 = "Bootsup Message" sent
Bit 9 = CANopen NMT State
Bit 10 = CANopen NMT State
Bit 11 = free
Bit 12 ... 14 = reserved
Bit 15 = free
CANopen NMT State Bit 10
Bit 9
Stopped =
Pre-Operational =
Operational =
0
0
1
0
1
0