13 setpoint card ± 10v, Setpoint card ± 10v, Fig. 8: dimensions of setpoint card± 10v – NORD Drivesystems BU0500 User Manual
Page 61: Table 22: rj45 wago connection module, Table 23: setpoint card ± 10v, 2 assembly and installation
2 Assembly and installation
BU 0500 GB-1013
61
Supplier
Name
Article number
WAGO Kontakttechnik GmbH
Ethernet connection module with CAGE CLAMP
connection
RJ45 transfer module
289-175
WAGO Kontakttechnik GmbH
Accessories: WAGO shield clamp
790-108
Alternative, complete connection module and shield clamp
Part No.
Getriebebau NORD GmbH &
Co.KG
Adapter module RJ45/terminal
278910300
Table 22: RJ45 WAGO connection module
Pos : 84 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 13 Soll wert kar te ± 10V [BU 0500] @ 0\ mod_1325866300204_388.doc x @ 6193 @ 2 @ 1
2.13 Setpoint card ± 10V
The analog inputs of series SK 500E frequency inverters size 1 to
4 can only process unipolar setpoints (0 … 10V; 0/4 20mA) with
reference to GROUND.
If a bipolar setpoint (analog difference signal (-10V … + 10V)) is
available, this must be converted to a 0 … 10V signal by means of
a setpoint converter. In this case, the appropriate module is
available from NORD. This module is suitable for snap-on rail-
mounting and should be installed near to the frequency inverter in
the control cabinet. For further details, please refer to the
supplementary instructions for the setpoint converter.
Note:
Frequency inverters of size S5 and above can process both unipolar and bipolar
setpoints by means of configuration with DIP switches.
Supplier
Name
Article number
Getriebebau NORD GmbH & Co.KG
Setpoint converter ±10V
→ 0 … 10V
278910320
Table 23: Setpoint card ± 10V
Fig. 8: Dimensions of setpoint card± 10V
Pos : 85 /Anl eitungen/ 3. /4. Anz eige und Bedienung [ BU 0500 / BU 0200] /SK 5xxE/ 3. Anzeige und Bedienung @ 0\ mod_1327492711496_388.doc x @ 6260 @ 1 @ 1
45
60
30
10