beautypg.com

P201 nominal motor frequency, P202 nominal speed, P203 nominal current – NORD Drivesystems BU0500 User Manual

Page 82

background image

SK 500E – Users Manual for Frequency Inverters

82

BU 0500 GB-1013

2 = 0.25kW 230V

3 = 0.33 Hp 230V

4 = 0.25kW 400V

5 = 0.33 Hp 460V

6 = 0.37kW 230V

7 = 0.50 Hp 230V

8 = 0.37kW 400V

9 = 0.50 Hp 460V

10 = 0.55kW 230V

11 = 0.75 Hp 230V

12 = 0.55kW 400V

13 = 0.75 Hp 460V

14 = 0.75 Hp 230V

15 = 1.0 Hp 230V

16 = 0.75 Hp 400V

17 = 1.0 Hp 460V

18 = 1.1 kW 230V

19 = 1.5 Hp 230V

20 = 1.1 kW 400V

21 = 1.5 Hp 460V

22 = 1.5 Hp 230V

23 = 2.0 Hp 230V

24 = 1.5 Hp 400V

25 = 2.0 Hp 460V

26 = 2.2 kW 230V

27 = 3.0 Hp 230V

28 = 2.2 kW 400V

29 = 3.0 Hp 460V

30 = 3.0 Hp 230V

31 = 3.0 Hp 400V

32 = 4.0 kW 230V

33 = 5.0 PS 230V

34 = 4.0 kW 400V

35 = 5.0 PS 460V

36 = 5.5 kW 230V

37 = 7.5 PS 230V

38 = 5.5 kW 400V

39 = 7.5 PS 460V

40 = 7.5 kW 230V

41 = 10.0 PS 230V

42 = 7.5 kW 400V

43 = 10.0 PS 460V

44 = 11.0 kW 400V

45 = 15.0 PS 460V

46 = 15.0 kW 400V

47 = 20.0 PS 460V

48 = 18.5 kW 400V

49 = 25.0 PS 460V

50 = 22.0 kW 400V

51 = 30.0 PS 460V

52 = 30.0 kW 400V

53 = 40.0 PS 460V

54 = 37.0 kW 400V

55 = 50.0 PS 460V

56 = 45.0 kW 400V

57 = 60.0 PS 460V

58 = 55.0 kW 400V

59 = 75.0 PS 460V

60 = 75.0 kW 400V

61 = 100.0 PS 460V

62 = 90.0 kW 400V

63 = 120.0 PS 460V

64 = 110.0 kW 400V

65 = 150.0 PS 460V

66 = 132.0 kW 400V

67 = 180.0 PS 460V

68 = 160.0 kW 400V

69 = 220.0 PS 460V

70 = 200.0 kW 400V

71 = 270.0 PS 460V

72 = 250.0 kW 400V

73 = 340.0 PS 460V

NOTE:

As P200 returns to = 0 after the input confirmation, the control of the set motor can be implemented
via parameter P205.

Information

IE2 motors

For the use of IE2 motors, after the selection of an IE1 motor (P200) the motor data in P201 ...
P209 must be adapted to the data on the motor type plate.

Pos : 121 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P201 – M ot or N ennfr equenz @ 0\ mod_1327588385923_388. doc x @ 7884 @ @ 1

P201

Nominal motor frequency

(Nominal motor frequency)

S

P

10.0 ... 399.9 Hz

{

***

}

The motor nominal frequency determines the V/f break point at which the FI supplies the nominal

voltage (P204) at the output.

Pos : 122 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P202 – M ot or N enndrehzahl @ 0\ mod_1327588441470_388. doc x @ 7907 @ @ 1

P202

Nominal speed

(Nominal motor speed)

S

P

150 ... 24000 rpm

{

***

}

The nominal motor speed is important for the correct calculation and control of the motor slip and
the speed display (P001 = 1).

Pos : 123 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P203 – M ot or N ennstr om @ 0\ mod_1327588500455_388.doc x @ 7930 @ @ 1

P203

Nominal current

(Nominal motor current)

S

P

0.1 ... 1000.0 A

{

***

}

The nominal motor current is a decisive parameter for the current vector control.

*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.