P529 mode load control – NORD Drivesystems BU0500 User Manual
Page 120
SK 500E – Users Manual for Frequency Inverters
120
BU 0500 GB-1013
P529
Mode Load control
(Load monitoring mode)
S
P
0 ... 3
{ 0 }
The reaction of the frequency inverter to an infringement of the defined monitoring range ((P525)
… (P527)) after the elapse of the delay time (P528) is specified by parameter (P529).
0 = Fault and warning, After the elapse of the time defined in (P528), an infringement of the
monitoring range produces a fault ("E12.5"). A warning ("C12.5") is given after the elapse
of half of this time.
1 = Warning, After the elapse of half of the time defined in (P528) and infringement of the
monitoring range produces a warning ("C12.5").
2 = Error and warning, constant travel, "Error and warning during constant travel", as for
setting "0" however monitoring is inactive during acceleration phases.
3 = Warning constant travel, "Only warning during constant travel", as for setting "1",
however monitoring is inactive during acceleration phases.
Pos : 288 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P525. .. P529 – Las tüber wac hung @ 0\ mod_1328093390150_388.doc x @ 11548 @ @ 1