P545 actual bus value 3, P546 digital bus setpoint 1, P547 digital bus setpoint 2 – NORD Drivesystems BU0500 User Manual
Page 126: P548 digital bus setpoint 3
SK 500E – Users Manual for Frequency Inverters
126
BU 0500 GB-1013
P545
Actual bus value 3
(Actual bus value 3)
S
P
0 ... 24
{ 0 }
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
Pos : 307 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P546 – Funkti on Bus-Soll wert 1 [ SK 500... 535E] @ 0\ mod_1328097962990_388. doc x @ 11916 @ @ 1
P546
Digital Bus setpoint 1
(Function of bus setpoint 1)
S
P
0 ... 55
{ 1 }
In this parameter, a function is allocated to the output setpoint 1 during bus actuation.
The possible analog functions can be found in the following table.
NOTE:
For further details please refer to the manual for the frequency inverter (P400, P546),
the relevant BUS operating instructions or the manuals BU 0510 / BU0550.
Pos : 309 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P546 – Funkti on Bus-Soll wert e, Ei nst ellungen [ SK 5xxE] @ 2\ mod_1354267859195_388.doc x @ 51897 @ @ 1
0 =
Off
16 = Process controller lead
1 =
Setpoint frequency
17 = BusIO In Bits 0...7
2 =
Torque current limit (P112)
18 = Curve travel calculator
3 =
Actual frequency PID
19 = Set relays, "Output status"
(P434/441/450/455=38)
4 =
Frequency addition
20 = Set analog output (P418=31)
5 =
Frequency subtraction
21 = ... 45 reserved from SK 530E and above
à
BU 0510
6 =
Current limit (P536)
46 = Setpoint Torque processreg., "Setpoint
torque process controller"
7 =
Maximum frequency (P105)
47 = reserved from SK 530E and above
à
BU 0510
8 =
Actual PID frequency limited
48 = Motor temperature (SK 540E and above)
9 =
Actual PID frequency monitored
49 = reserved from SK 540E and above
à
BU 0510
10 = Torque servo mode (P300)
53 = d-correction F process (SK 540E and
above)
11 = Torque precontrol (P214)
54 = d-correction Torque (SK 540E and above)
12 = Reserved
55 = d-correction F+torque (SK 540E and
above)
13 = Multiplication
56 = reserved from SK 540E and above
à
BU 0510
14 = Process controller actual value
57 = reserved from SK 540E and above
à
BU 0510
15 = Process controller setpoint
Scaling details: See Section 8.8
Pos : 310 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P547 – Funkti on Bus-Soll wert 2 [ SK 500... 535E] @ 0\ mod_1328098180008_388. doc x @ 11962 @ @ 1
P547
Digital Bus setpoint 2
(Function of bus setpoint 2)
S
P
0 ... 55
{ 0 }
This parameter is identical to P546.
Pos : 311 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P548 – Funkti on Bus-Soll wert 3 [ SK 500... 535E] @ 0\ mod_1328098278323_388. doc x @ 11985 @ @ 1
P548
Digital Bus setpoint 3
(Function of bus setpoint 3)
S
P
0 ... 55
{ 0 }
This parameter is identical to P546.
Pos : 312 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P549 – Funkti on Poti-Box @ 0\ mod_1328098389279_388. doc x @ 12008 @ @ 1