2.8 Output choke SK CO1

To reduce interference signals from the
motor cable or to compensate for cable
capacitance in long motor cables, an
additional output choke can be installed
into the inverter output.

During installation take care that the pulse
frequency of the frequency inverter is set
to 3 - 6 kHz (P504 = 3 - 6).

These chokes are specified for a
maximum supply voltage of 480 V at
0 - 100 Hz.

An output choke should be fitted for cable lengths over 100 m/30 m (unshielded/shielded). All chokes

have a protection class corresponding to

IP00. The choke used must therefore be installed in a control

cabinet.

Inverter ID

NORD

SK 5xxE

Output choke 3 x200 – 240 V

L1

W1

D

Detail: Mounting

C

o

n

n

e

c

ti

o

n

Type

Continuous

current

Inductance

L2

B2

In

st

al

lat

ion

0.25 … 0.75

kW

SK CI1-460/4-C

Part. No.: 276996004

4 A

3 x 3.5 mH

120

104

140

84

75

M6

4

1.1 ... 1.5 kW

SK CI1-460/9-C

Part. No.: 276996009

9 A

3 x 2.5 mH

155

110

160

130

71.5

M6

4

2.2 ... 4.0 kW

SK CI1-460/17-C

Part. No.: 276996017

17 A

3 x 1.2 mH

185

102

201

170

57.5

M6

10

5.5 ... 7.5 kW

SK CI1-460/33-C

Part. No.: 276996033

33 A

3 x 0.6 mH

185

122

201

170

77.5

M6

10

11 … 15 kW

SK CI1-480/60-C

Part. No.: 276992060

60 A

3 x 0.33 mH 185

112

210

170

67

M8

16

18 kW

SK CI1-460/90-C

Part. No.: 276996090

90 A

3 x 0.22 mH 352

144

325

224

94

M10

35

All dimensions in [mm]

[mm

2

]

Table 12: Output choke data for SK CO1-..., 3~ 240 V

D

L2

L1

W1

B2

U

V

V2

U2

W

W3

Similar to
illustration