2.8 Output choke SK CO1
To reduce interference signals from the
motor cable or to compensate for cable
capacitance in long motor cables, an
additional output choke can be installed
into the inverter output.
During installation take care that the pulse
frequency of the frequency inverter is set
to 3 - 6 kHz (P504 = 3 - 6).
These chokes are specified for a
maximum supply voltage of 480 V at
0 - 100 Hz.
An output choke should be fitted for cable lengths over 100 m/30 m (unshielded/shielded). All chokes
have a protection class corresponding to
IP00. The choke used must therefore be installed in a control
cabinet.
Inverter ID
NORD
SK 5xxE
Output choke 3 x200 – 240 V
L1
W1
D
Detail: Mounting
C
o
n
n
e
c
ti
o
n
Type
Continuous
current
Inductance
L2
B2
In
st
al
lat
ion
0.25 … 0.75
kW
SK CI1-460/4-C
Part. No.: 276996004
4 A
3 x 3.5 mH
120
104
140
84
75
M6
4
1.1 ... 1.5 kW
SK CI1-460/9-C
Part. No.: 276996009
9 A
3 x 2.5 mH
155
110
160
130
71.5
M6
4
2.2 ... 4.0 kW
SK CI1-460/17-C
Part. No.: 276996017
17 A
3 x 1.2 mH
185
102
201
170
57.5
M6
10
5.5 ... 7.5 kW
SK CI1-460/33-C
Part. No.: 276996033
33 A
3 x 0.6 mH
185
122
201
170
77.5
M6
10
11 … 15 kW
SK CI1-480/60-C
Part. No.: 276992060
60 A
3 x 0.33 mH 185
112
210
170
67
M8
16
18 kW
SK CI1-460/90-C
Part. No.: 276996090
90 A
3 x 0.22 mH 352
144
325
224
94
M10
35
All dimensions in [mm]
[mm
2
]
Table 12: Output choke data for SK CO1-..., 3~ 240 V