NORD Drivesystems BU0500 User Manual
Page 89
5 Parameters
BU 0500 GB-1013
89
P314
Torque current controller limit
(Torque current controller limit)
S
P
0 ... 400 V
{ 400 }
Determines the maximum voltage increase of the torque current controller. The higher the value,
the greater the maximum effect that can be exercised by the torque current controller. Excessive
values in P314 can specifically lead to instability during transition to the field weakening zone (see
P320). The values for P314 and P317 should always be set roughly the same, so that the field
and torque current controllers are balanced.
Pos : 154 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P315 – Fel dstr omr egler P @ 1\ mod_1328618593561_388.doc x @ 15410 @ @ 1
P315
Field current controller P
(Field current controller P)
S
P
0 ... 800 %
{ 200 }
Current controller for the field current. The higher the current controller parameters are set, the
more precisely the current setpoint is maintained. Excessively high values for P315 generally lead
to high frequency vibrations at low speeds. On the other hand, excessively high values in P316
generally produce low frequency vibrations across the whole speed range If the value "Zero" is
entered in P315 and P316, then the field current controller is switched off. In this case, only the
motor model pre-control is used.
Pos : 155 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P316 – Fel dstr omr egler I @ 0\ mod_1327592705182_388. doc x @ 8676 @ @ 1
P316
Field current controller I
(Field current controller I)
S
P
0 ... 800 % / ms
{ 125 }
I-proportion of the field current controller. See also P315 >Field current controller P<
Pos : 156 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P317 – Grenz e F elds tromr egler @ 0\ mod_1327592747463_388. doc x @ 8699 @ @ 1
P317
Field current controller limit
(Field current controller limit)
S
P
0 ... 400 V
{ 400 }
Determines the maximum voltage increase of the field current controller. The higher the value, the
greater is the maximum effect that can be exercised by the field current controller. Excessive
values in P317 can specifically lead to instability during transition to the field reduction range (see
P320). The values for P314 and P317 should always be set roughly the same, so that the field
and torque current controllers are balanced.
Pos : 157 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P318 – Fel dsc hwäc hregl er P @ 0\ mod_1327592793650_388. doc x @ 8722 @ @ 1
P318
Field weakening controller P
(Field weakening controller P)
S
P
0 ... 800 %
{ 150 }
The field weakening controller reduces the field setpoint when the synchronous speed is
exceeded. Generally, the field weakening controller has no function; for this reason, the field
weakening controller only needs to be set if speeds are set above the nominal motor speed.
Excessive values for P318 / P319 will lead to controller oscillations. The field is not weakened
sufficiently if the values are too small or during dynamic acceleration and/or delay times. The
downstream current controller can no longer read the current setpoint.
Pos : 158 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P319 – Fel dsc hwäc hregl er I @ 0\ mod_1327677030485_388. doc x @ 8750 @ @ 1
P319
Field weakening controller I
(Field weakening controller I)
S
P
0 ... 800 % / ms
{ 20 }
Only affects the field weakening range, see P318 >Field weakening controller P<
Pos : 159 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P320 – Grenz e F elds chwäc hregler @ 0\ mod_1327677173911_388. doc x @ 8773 @ @ 1