8.2.2 Process controller parameter settings
Example: SK 500E, setpoint frequency: 50 Hz, control limits: +/- 25%
P105 (maximum frequency)
[Hz]
[ ]
[ ]
[ ]
ч
ш
ц
з
и
ж
´
+
³
100%
Hz
%
P415
Hz
q.
Setpointfr
q.
Setpointfr
Example:
=
´
+
³
%
100
%
25
50
50
Hz
Hz
62.5Hz
P400 (Funct. analog input):
„4“ (frequency addition)
P411 (setpoint frequency) [Hz]
Set frequency with 10 V at analog input 1
Example: 50 Hz
P412 (Process controller
setpoint):
CR middle position / Default setting 5V (adjust if necessary)
P413 (P controller) [%]:
Factory setting 10% (adjust if necessary)
P414 (I-controller) [% / ms]:
recommended 100%/s
P415 (limitation +/-) [%]
Controller limitation (see above)
Note:
In the function process controller, parameter P415 is used as a
controller limiter downstream from the PI controller. This
parameter therefore has a double function.
Example: 25% of setpoint
P416 (ramp before controller)
[s]:
Factory setting 2s (if necessary, adjust to match controller
behaviour)
P420 (Funct. digital input 1):
"1" Enable right
P405 (Funct. Analoginput 2):
„14“ actual value PID process controller
Controller limit
P415 in % of
setpoint
Controller limit
P415
f
t