P552, Can master circle, P554 chopper min. threshold – NORD Drivesystems BU0500 User Manual

Page 128

background image

SK 500E – Users Manual for Frequency Inverters

128

BU 0500 GB-1013

P552

[-01]

[-02]

CAN master circle

(CAN master cycle time)

S

0 … 100 ms

{ all 0 }

In this parameter, the cycle time for the CAN/CANopen master mode and the CANopen encoder
is set (see P503/514/515):

[-01] = CAN Master function, cycle time for CAN/CANopen Master functionality

[-02] = CANopen absolute encoder, cycle time of CANopen absolute encoder

According to the Baud rate set, there are different minimum values for the actual cycle time:

Baud rate

Minimum value t

Z

Default CAN Master

Default CANopen Abs.

10kBaud

10ms

50ms

20ms

20kBaud

10ms

25ms

20ms

50kBaud

5ms

10ms

10ms

100kBaud

2ms

5ms

5ms

125kBaud

2ms

5ms

5ms

250kBaud

1ms

5ms

2ms

500kBaud

1ms

5ms

2ms

1000kBaud:

1ms

5ms

2ms

The range of values which can be set is between 0 and 100ms. With the setting 0 “Auto” the
default value (see table) is used. The monitoring function for the CANopen absolute encoder no
longer triggers at 50ms, but rather at 150ms.

Pos : 317 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P554 – Mi ni mal er Ei ns atz punkt C hopper @ 0\ mod_1328098628171_388.doc x @ 12100 @ @ 1

P554

Chopper min. threshold

(Minimum chopper threshold)

S

65 ... 101 %

{ 65 }

The switching threshold of the brake chopper can be influenced with this parameter. An optimized
value for numerous applications is set in the factory setting. This parameter can be increased for
applications where pulsating energy is returned (crank drives) to minimise brake resistance power
dissipation.

An increase in this setting leads to a faster overvoltage switch off of the FI.

The setting 101% also switches off the brake chopper at the 65% switching threshold. In addition,
with this setting, monitoring is also active if the FI has not been enabled. I.e. for example if the link
circuit voltage in the FI increases above the threshold in "Standby" status (e.g. due to a mains
fault), the brake chopper is activated. However, in case of an FI fault, the brake chopper is
generally inactive.