6 Operating status messages
BU 0500 GB-1013
143
E008
8.0
Parameter loss
(maximum EEPROM value
exceeded)
Error in EEPROM data
•
The software version of the stored data set is not
compatible with the software version of the FI.
NOTE:
Faulty parameters are automatically reloaded
(default setting).
•
EMC faults (see also E020)
8.1
Inverter type incorrect
•
EEPROM faulty
8.2
External copying error
(ControlBox)
•
Check ControlBox for correct position.
•
ControlBox EEPROM faulty (P550 = 1).
8.3
EEPROM KSE error
(Customer interface incorrectly
identified (customer’s interface
equipment))
The upgrade level of the frequency inverter was not
correctly identified.
•
Switch mains voltage off and on again.
8.4
Internal EEPROM error
(Database version incorrect)
8.7
EEPR copy not the same
Pos : 406 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E009 [ SK 5xxE] @ 2\ mod_1361521138476_388. doc x @ 58991 @ @ 1
E009
---
Display in ParameterBox not
required
ControlBox error/ SimpleBox error
SPI Bus faulty, no communication with ControlBox /
SimpleBox
•
Check ControlBox for correct position.
•
Check correct cabling of SimpleBox.
•
Switch mains voltage off and on again.
Pos : 407 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E010 [ SK 500E ... SK 535E] @ 2\ mod_1361522985031_388.doc x @ 59041 @ @ 1
E010
10.0
Bus Timeout
Telegram time-out / Bus off 24V int. CANbus)
Data transfer is faulty. Check P513.
•
Check external Bus connection.
•
Check the program sequence of the Bus protocol
•
Check Bus Master.
•
Check 24V supply of internal CAN/CANopen Bus.
•
Nodeguarding error (internal CANopen)
•
Bus Off error (internal CANbus)
10.2
Bus Timeout Option
Bus module telegram timeout
•
Telegram transfer is faulty.
•
Check external connection.
•
Check bus protocol program sequence.
•
Check Bus Master.
10.4
Init error Option
Bus module initialisation failure
•
Check Bus module power supply.
•
Check P746.
•
Bus module not correctly plugged in.
10.1
System error option
Bus module system error
•
Further details can be found in the respective
supplementary Bus operating instructions.
10.3
10.5
10.6
10.7
10.8
Option error
External module communication failure
•
Connection fault / error in the external module
•
Brief interruption (<1sec) of the 24 V supply of the
internal CAN/CANopen bus
Pos : 409 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E011 [ SK 180E ... SK 5xxE] @ 2\ mod_1347453318765_388.doc x @ 46626 @ @ 1