Terminal block x5 – digital in, 2 assembly and installation – NORD Drivesystems BU0500 User Manual
Page 51
![background image](/manuals/372731/51/background.png)
2 Assembly and installation
BU 0500 GB-1013
51
Terminal block X5 – Digital In
Relevance
SK 500E
SK 505E
SK 510E
SK 511E
SK 515E
SK 520E
SK 530E
SK 535E
√
√
√
√
√
Terminals X5:
21
22
23
24
25
42
40
41
DIN1
DIN2
DIN3
DIN4
DIN5
VO 15V
GND/0V
VO 5V
Name
Terminal Function
[factory setting]
Data
Description / wiring suggestion
Parameter
21
Digital input 1
[ON right]
7.5...30V, R
i
=6.1k
W
Not suitable for thermistor
evaluation.
HTL encoders can only be
connected to DIN2 and
DIN4
Limiting frequencies:
max.
10 kHz
min.
15 Hz
Each digital input has a reaction time of
≤ 5ms.
Connection with internal 15V:
21
22
23
24
25
42
40
41
15V
motor - PTC
Connection with external 7,5-30V:
21
22
23
24
25
42
40
41
7.5 … 30V
motor - PTC
GND / 0V
P420
22
Digital input 2
[ON left]
P421
23
Digital input 3
[parameter set bit0]
P422
24
Digital input 4
[Fixed frequency 1,
P429]
P423
25
Digital input 5
[no function]
2.5...30V, R
i
=2.2k
W
Not suitable for evaluation
of a safety device.
Suitable for thermistor
evaluation with 5V.
NOTE: For the motor
thermistor P424 = 13 must
be set.
P424
42
15V output power
supply
15V
± 20%
Supply voltage provided by the
frequency inverter for connection to the
digital inputs or the supply of a 10-30V
encoder.
40
Reference potential
for digital signals
0V digital
Reference potential
41
5V output power
supply
5V
± 20%
Voltage supply for motor-PTC