5 parameters, P542 set analog output, P543 actual bus value 1 – NORD Drivesystems BU0500 User Manual

Page 125: P544 actual bus value 2

background image

5 Parameters

BU 0500 GB-1013

125

Pos : 300 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P542 – Anal ogausgang setz en [SK 500. .. 535E] @ 0\ mod_1328093953369_388. doc x @ 11778 @ @ 1

P542

Set analog output

(Set analog output)

S

0.0 ... 10.0 V

{ 0.0 }

The analog output of the FI can be set with this function, independently of the actual operating state.
To do this, the relevant analog output must be set to the function "External control" (P418 = 7).

This function can either be used manually or in combination with a bus control. The value set here
will, once confirmed, be produced at the analog output.

NOTE:

The setting is not saved in the EEPROM and is lost when the frequency inverter is
switched off!

Pos : 302 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P543 – Bus-Ist wert 1 [SK 500. .. 535E] @ 0\ mod_1328097541755_388.doc x @ 11824 @ @ 1

P543

Actual bus value 1

(Actual bus value 3)

S

P

0 ... 24

{ 1 }

The return value 1 can be selected for bus actuation in this parameter.

The possible analog functions can be found in the following table.

NOTE:

For further details please refer to the manual for the frequency inverter (P418, P543),

the relevant BUS operating instructions or BU 0510.

Pos : 304 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P543 - Bus- Is t wer te, Ei nst ellungen [ SK 5xxE] @ 2\ mod_1354267251544_388.doc x @ 51871 @ @ 1

0 =

Off

13 = ... 16 Reserved

1 =

Actual frequency

17 = Value analog input 1

2 =

Actual speed

18 = Value analog input 2

3 =

Current

19 = Setpoint frequency master

value(P503)

4 =

Torque current (100% = P112)

20 = Setpoint frequency master value after

ramp "Setpoint frequency master
value after ramp"

5 =

Digital IO status

1

21 = Act. freq. without slip master value

"Actual frequency without slip master
value"

6 =

... 7 Reserved

22 = Speed encoder 


(only possible with

SK 520E and encoder feedback)

8 =

Setpoint frequency

23 = Actual frequency with slip, "Actual

frequency with slip"

(SW V2.0 and above)

9 =

Error number

24 = Master value, actual freq. with slip,

"Master value, actual freq. with slip"

(SW V2.0 and above)

10 = ... 11 Reserved

53 = ... 57 Reserved

12 = BusIO Out Bits 0...7

Scaling details: Section: 8.8

Pos : 305 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P544 – Bus-Ist wert 2 [SK 500. .. 535E] @ 0\ mod_1328097766412_388.doc x @ 11870 @ @ 1

P544

Actual bus value 2

(Actual bus value 2)

S

P

0 ... 24

{ 0 }

This parameter is identical to P543.

Condition is PPO 2 or PPO 4 type (P507).

Pos : 306 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P545 – Bus-Ist wert 3 [SK 500. .. 535E] @ 0\ mod_1328097880052_388.doc x @ 11893 @ @ 1

1

The assignment of the digital inputs in P543/ 544/ 545 = 5

Bit 0 = DigIn 1

Bit 1 = DigIn 2

Bit 2 = DigIn 3

Bit 3 = DigIn 4

Bit 4 = DigIn 5

Bit 5 = DigIn 6 (SK 520E and above)

Bit 6 = DigIn 7 (SK 520E and above)

Bit 7 = Dig. func. AIN1

Bit 8 = Dig. func. AIN1 AIN2

Bit 9 = DigIn 8 (SK 540E and above)

Bit 10 = DigIn 1, 1.IOE (SK 540E and above)

Bit 11 = DigIn 2, 1.IOE (SK 540E and above)

Bit 12 = Out 1/ MFR1

Bit 13 = Out 2/ MFR2

Bit 14 = Out 3/ DOUT1 (SK 520E and above)

Bit 15 = Out 4/ DOUT2 (SK 520E and above)