beautypg.com

3 reduced overcurrent due to output frequency, Reduced overcurrent due to output frequency, Table 31: overcurrent relative to time – NORD Drivesystems BU0500 User Manual

Page 165: 8 additional information

background image

8 Additional information

BU 0500 GB-1013

165

230V devices: Reduced overload capacity (approx.) due to pulse frequency (P504) and time

Pulse frequency
[kHz]

Time [s]

> 600

60

30

20

10

3.5

3...8

110%

150%

170%

180%

180%

200%

10

103%

140%

155%

165%

165%

180%

12

96%

130%

145%

155%

155%

160%

14

90%

120%

135%

145%

145%

150%

16

82%

110%

125%

135%

135%

140%

400V devices: Reduced overload capacity (approx.) due to pulse frequency (P504) and time

Pulse frequency
[kHz]

Time [s]

> 600

60

30

20

10

3.5

3...6

110%

150%

170%

180%

180%

200%

8

100%

135%

150%

160%

160%

165%

10

90%

120%

135%

145%

145%

150%

12

78%

105%

120%

125%

125%

130%

14

67%

92%

104%

110%

110%

115%

16

57%

77%

87%

92%

92%

100%

Table 31: Overcurrent relative to time

Pos : 452 /Anleit ungen/8. / 9. Zusatzinfor mationen [BU 0500 / BU 0200]/ 8. 5. 3 R eduzi erter Überstrom aufgrund der Ausgangsfrequenz @ 0\ mod_1328188934696_388.doc x @ 14351 @ 3 @ 1

8.5.3 Reduced overcurrent due to output frequency

To protect the power unit at low output frequencies (<4.5Hz) a monitoring system is provided, with
which the temperature of the IGBTs (integrated gate bipolar transistor) due to high current is
determined. In order to prevent current being taken off above the limit shown in the diagram, a pulse
switch-off (P537) with a variable limit is introduced. At a standstill, with 6kHz pulse frequency, current
above 1.1x the nominal current cannot be taken off.

x f

( )

In_ 60s ec f

( )

In_ 1sec f

( )

f

0

2

4

6

8

10

12

14

16

18

20

0

0.5

1

1.5

2

2.5

I / I

N

Output frequency [Hz]

Prohibited region