2 electrical data, 1 electrical data 115v, Electrical data – NORD Drivesystems BU0500 User Manual
Page 150: Electrical data 115v
SK 500E – Users Manual for Frequency Inverters
150
BU 0500 GB-1013
Pos : 437 /Anleit ungen/7. / 8. Technisc he Daten [BU 0500/ BU 0200] /SK 5xxE/ 7. 2 El ektrisc he D aten @ 0\ mod_1328183290738_388. doc x @ 14006 @ 2 @ 1
7.2 Electrical data
The following tables include the data relevant for UL.
Details of the UL /cUL approval conditions can be found in Section 0 Use of mains fuses which are
faster than those stated is permissible.
Pos : 438 /Anleit ungen/7. / 8. Technisc he Daten [BU 0500/ BU 0200] /SK 5xxE/ 7. 2.1 El ektrisc he Daten 115V @ 0\ mod_1328183334081_388.doc x @ 14029 @ 3 @ 1
7.2.1 Electrical data 115V
FI type (size 1):
SK 5xxE…
-250-112-O
-370-112-O
-550-112-O
-750-112-O
-111-112-O
Nominal motor power
(4-pole standard motor)
230V
0.25hp
0.37 kW
0.55 kW
0.75hp
1.10 kW**
240V
1
/
3
hp
½ hp
¾ hp
1 hp
1 ½ hp**
Input
Mains voltage
1~ 115V
1 AC 110 … 120V,
± 10%, 47 … 63Hz
Input current
1~ rms
8.9 A
11.0 A
13.1 A
20.1 A
23.5 A
1~ FLA
8.9 A
10.8 A
13.1 A
20.1 A
23.5 A
Recommended mains
fuse*
1 AC slow-
acting
10 A
15 A
15 A
20 A
25 A
CB
10 A
15 A
25 A
20 A
25 A
Permissible mains
fuses for UL*
Fuse, 300V
10 A
20 A
20 A
25 A
25 A
Bussmann
FRS-R-10
FRS-R-15
FRS-R-20
FRS-R-25
FRS-R-25
CB
10 A
15 A
20 A
25 A
25 A
O
ut
put
Output voltage
3~ 230V
3 AC 0 – 2x mains voltage
Output current
rms
1.7 A
2.2 A
3.0 A
4.0 A
5.3 A
FLA
1.7 A
2.1 A
3.0 A
4.0 A
5.3 A
Min. braking resistor
Accessories
240
W
190
W
140
W
100
W
75
W
Type of ventilation
Free convection
Fan cooling, temperature-controlled
Switching thresholds:
ON= 57°C OFF=47°C
Weight
Approx. [kg]
1.4
* see also Section 1.5.2. Fuses: High-Interrupting Capacity, Current Limiting Classes (z.B. R, J, …), circuit breaker (CB): Inverse Time Trip Type
** S3 / 80 % 10 Min.