Setting for unbalance rate measurement, Setting for interval, Setting for output threshold – KYORITSU 6310 Instruction Manual User Manual
Page 94
![background image](/manuals/369632/94/background.png)
4.2.2 Measurement Setting (QUALITY-Voltage Unbalance Ratio KEW6310
4.53
KEW6310
Setting for unbalance rate measurement
For the details of Voltage Unbalance Rate Measurement, refer to “11.5 Unbalance Rate” in this manual.
Setting Items
Interval :
set
interval time
Output threshold
: set threshold for the output of voltage unbalance rate
Setting for interval
* Default value (or after system reset) : 30 min
* Setting procedure is same to that for interval Setting for W/ Wh/ DEMAND.Refer to the procedure described in
the preceding pages.
Setting for output threshold
1 ~ 20% (can be set by 0.1%)
* Default value (or after system reset) : 3%
1
Press the
Cursor
Keys and select [Output Threshold], and then press the
ENTER
Key.
2
Press the
Cursor
Keys and alter values, and then press the
ENTER
Key.
Box with
▲▼
mark appears
at the rightmost digit.
Selected output threshold
is displayed.