Timing of data recording, Recording at event occurrence, Recording at every interval – KYORITSU 6310 Instruction Manual User Manual
Page 226
11.4.2 Power quality – Measuring procedure (Inrush current measurement) KEW6310
11.21
KEW6310
Timing of data recording
<
Recording at event occurrence>
<
Recording at every interval>
* Function available with ver2.00 or later.
Start
End
100%
(Reference)
current
110%
(
Threshold
vallue)
109%
(Thresholc value110%-Hysteresis1%)
100
data pts
100
data pts
Trigger
Trigge
r
100
data pts
100
data pts
201 data pts
recorded
Duration
RMS(max)
201 data pts
recorded
Interval
Ave,max and min values within
each interval are recording.
※
Inst value : Avg of 100 data (@50Hz) obtained in the preset inst
interval of 1sec(RMS)
Avg value : Avg of rms values obtained in the preset inst interval
Max value : Max rms values obtained in the preset inst interval
Min value : Min rms values obtained in the preset inst interval.
Inst values recorded at
every interval.