KEW6310 4.2.2 Measurement Setting (QUALITY-Inrush Current Measurement)
KEW6310
4.52
1
Press the
Cursor
Keys and select [A_Referene], and then press the
ENTER
Key.
2
Press the
Cursor
Keys and alter the values, and press the
ENTER
Key to fix it.
Setting for Threshold
100 ~ 200% (can be set by 1%)
* Default value (or after system reset) : 110%
* Setting procedure is same to that for Threshold Setting for Swell, Dip, int measurement.
Refer to the procedure described in the preceding pages.
Setting for hysteresis
1 ~ 10% (can be set by 1%)
* Default value (or after system reset) : 5%
* Setting procedure is same to that for Hysteresis Setting for Swell, Dip, Int measurement.
Refer to the procedure described in the preceding pages.
Setting for trigger point
Past: 0 ~ 200 (can be set by 1)
Next : 200 ~ 0 (can be set by 1)
* Default value (or after system reset) : 100
* Trigger to start and stop recording, when a preset threshold exceeded, will be decided based
on the number of recorded data.
* Setting procedure is same to that for Trigger Point Setting for Swell, Dip, Int measurement.
Refer to the procedure described in the preceding pages.
Box with
▲▼
mark appears
at the rightmost digit.
Selected reference current
is displayed.