Setting for dip – KYORITSU 6310 Instruction Manual User Manual
Page 82

KEW6310 4.2.2 Measurement Setting (QUALITY-Swell, Dip, INT Measurement)
4.41
KEW6310
Setting for dip
5~ 100% (can be set by 1%)
* Default value (or after system reset) : 90%
1
Press the
Cursor
Keys and select [Dip], and then press the
ENTER
Key.
2
Press the
Cursor
Keys and alter values, and then press the
ENTER
Key.
Lower limit varies depending on the selected reference voltage.
● 70 ~ 150V : percentage to obtain values of 7.5 or more 
● 151 ~ 300V : percentage to obtain values of 15.0 or more 
● 301 ~ 600V : percentage to obtain values of 30.0 or more 
● 601 ~ 1000V : percentage to obtain values of 50.0 or more 
Box with
▲▼
mark appears
at the rightmost digit.
Selected dip is displayed.
                    See also other documents in the category KYORITSU Tools:                                                            
                    - 1009 (13 pages)
 - 1011 (12 pages)
 - 1012 (12 pages)
 - 1018 (1 page)
 - 1030 (1 page)
 - 1061 (58 pages)
 - 1051 (40 pages)
 - 1109S (36 pages)
 - 1110 (1 page)
 - 2000 (1 page)
 - 2002PA (27 pages)
 - 2007A (1 page)
 - 2009R (33 pages)
 - 2012R (2 pages)
 - 2017 (1 page)
 - 2031 (1 page)
 - 2033 (9 pages)
 - 2040 (2 pages)
 - 2046R (2 pages)
 - 2200 (3 pages)
 - 2210R (1 page)
 - 2300R (1 page)
 - 2413F (24 pages)
 - 2413R (24 pages)
 - 2431 (2 pages)
 - 2432 (1 page)
 - 2433R (1 page)
 - 2434 (10 pages)
 - 2500 (1 page)
 - 2608A (2 pages)
 - 3005A (24 pages)
 - 3021 (24 pages)
 - 3121A (12 pages)
 - 3126 (28 pages)
 - 3127 (60 pages)
 - 3128 (88 pages)
 - 3131A (20 pages)
 - 3132A (20 pages)
 - 3161A (24 pages)
 - 3321A (24 pages)
 - 4105A (10 pages)
 - 4106 (48 pages)
 - 4116A (20 pages)
 - 4140 (32 pages)
 - 4200 (24 pages)
 