Operation – KROHNE OPTISONIC 6300 EN User Manual
Page 89
OPERATION
6
89
OPTISONIC 6300
www.krohne.com
07/2009 - 4000263902 - HB OPTISONIC 6300 R03 en
C5.2.12
threshold
inactive if C5.2.11 is set to off: set
lag value between normal and
extended range
min-max: 05.0 - 80.0
C5.2.13
information
serial number of circuit board,
software version, calibration date
of circuit board
C5.2.14
simulation A
simulation of current output A
set value:on/off, cancel min-max: 00.0 - 22.0
mA
C5.2.15
4 mA trimming
restore factory setting for 4 mA
min-max: 3.6000 - 5.5000 mA
C5.2.16
20 mA trimming
restore factory setting for 20 mA
min-max: 18.500 - 21.500 mA
C5.3
C5.3
C5.3
C5.3
frequency output
frequency output
frequency output
frequency output
C5.3.1
pulse shape
set shape
symmetric, automatic, fixed
C5.3.2
pulse width
active if C2.3.1 is set to fixed: set
time for pulse activation
min-max: 0000.05 - 2000.00
C5.3.3
100 % pulse rate
min-max: 00000.0 - 10000.0
C5.3.4
measurement
measurement value to frequency
output
(depends on pipe configuration: 1 or 2 pipes)
volume flow, mass flow, VoS, flow speed, gain,
SNR, diagnosis value, volume flow 1 or 2, VoS 1
or 2
C5.3.5
range
set measurement range from 0
to 100 %
(min-max depends on parameter settings)
C5.3.6
polarity
set polarity of frequency output
both polarities
C5.3.7
limitation
set lower and upper limit for
frequency output
min-max: -150 - +150 %
C5.3.8
low flow cutoff
set low values to zero
min-max: 00.0 - 20.0
C5.3.9
time constant
within set time, measurements
are averaged, displayed and sent
to current output
min-max: 000.1 - 100.0
C5.3.10
invert signal
define frequency output
activation
off: activate high current/switch closed
on: low current/switch open
C5.3.11
phase shift
phase shift between output B and
D
0, 90, 180 degrees
C5.3.12
special function
for ranging
off, phase shift
C5.3.13
information
C5.3.14
simulation
simulation of frequency output
on, off, cancel
C5.4
C5.4
C5.4
C5.4
pulse output
pulse output
pulse output
pulse output
C5.4.1
pulse shape
set shape
symmetric, automatic, fixed
C5.4.2
pulse width
set time for pulse activation
available if pulse shape is set: fixed min-max:
0000.05 - 2000.00
C5.4.3
max. pulse rate
min-max: 00000.0 - 10000.0 Hz
C5.4.4
measurement
measurement value to pulse
output
(depends on pipe configuration: 1 or 2 pipes)
volume flow, mass flow, volume flow 1 or 2
C5.4.5
pulse value unit
unit for pulse output
mL, L, free unit
C5.4.6
value p. pulse
value of pulse per volume or
mass for pulse output
no min-max
C5.4.7
polarity
set polarity of pulse output
positive -, negative -, both polarity(ies), absolute
value
C5.4.8
low flow cutoff
set low values to zero
min-max: 00.0 - 20.0
C5.4.9
time constant
within set time, measurements
are averaged, displayed and sent
to current output
min-max: 000.1 - 100.0
C5.4.10
invert signal
activate switch closed, open
off, on
.book Page 89 Tuesday, August 18, 2009 4:51 PM