Start-up – KROHNE OPTISONIC 6300 EN User Manual
Page 59
START-UP
5
59
OPTISONIC 6300
www.krohne.com
07/2009 - 4000263902 - HB OPTISONIC 6300 R03 en
if no:
if no:
if no:
if no:
copy pipe 1 data appears
Go to X7
Fill in menu X7.2 up to X7.13:
is similar to X6.2 up to X6.13
^
if yes:
if yes:
if yes:
if yes:
copy pipe 1 data appears
after copy process
^
X9...X10
X9
install transd. 1
> X9.1, X9.2,…
↑ ↓
X9.1
transducer set
> read preset Ta,Tb,Tc /
confirm or overrule using ↑ ↓
>
X9.2
calibration number
read
^
X9.3
number of
traverses
> read preset 1,2,4 / confirm or
overrule using ↑ ↓ >
X9.4
mount transducers
at
read advise
^
please wait: decounting 30 seconds
X9.5
act. flow,
preliminary
read
^
X9.6
check signal
read (0 - 100 %)
^
X9.7
actual distance
> fill in using ↑ ↓ >
^
(start optimization loop)
X9.8.1
optimize distance ?
yes/no
^
if no:
go to X9.9
if yes:
continue with X9.8.2
X9.8.2
act. VoS fluid
read
^
X9.8.3
continue ?
yes/no
^
if no:
go to X9.9
if yes:
continue with X9.8.4
X9.8.4
VoS fluid
read / confirm or overrule
using ↑ ↓ >
^
X9.8.5
mount transducers
at
read advise
^
(end optimization loop; next menu appearing is X9.8.1)
(underneath X10 becomes active if two pipes or two paths
(underneath X10 becomes active if two pipes or two paths
(underneath X10 becomes active if two pipes or two paths
(underneath X10 becomes active if two pipes or two paths are selected in X4 or X5)
X10
install transd. 2
>
↑ ↓
submenus identical to X9.1
up to X9.12
^
.book Page 59 Tuesday, August 18, 2009 4:51 PM