Technical data, 2 technical data – KROHNE OPTISONIC 6300 EN User Manual

Page 107

background image

TECHNICAL DATA

8

107

OPTISONIC 6300

www.krohne.com

07/2009 - 4000263902 - HB OPTISONIC 6300 R03 en

8.2 Technical data

INFORMATION!

The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local representative.

Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Downloadcenter).

Measuring system

Measuring principle

Ultrasonic transit time

Application range

Flow measurement of liquids

Measured value

Measured value

Measured value

Measured value

Primary measured value

Transit time

Secondary measured value

Volume flow, mass flow, flow speed, flow direction, speed of sound,

gain, signal to noise ratio, diagnosis value, reliability of flow

measurement, quality of acoustic signal

Design

The measurement system consists of a measuring sensor and a

signal converter. It is only available as separate version.

Signal converter

Signal converter

Signal converter

Signal converter

Wall-mounted housing (W) -

remote version

UFC 300 W (general purpose)

Field housing (F) - remote

version

UFC 300 F (Option: Ex version)

Measuring sensor

Measuring sensor

Measuring sensor

Measuring sensor

Standard

Small, medium or large version in aluminum

Optional

Small / medium stainless steel version

Small / medium XT (eXtended Temperature).

Diameter ranges

Diameter ranges

Diameter ranges

Diameter ranges

Small

DN15...100 / ½…4"

Outer diameter must be at least 20 mm / 0.79".

Medium

DN50...400 / 2…16"

Large

DN200...4000 / 8…160"

Outer diameter must be smaller than 4300 mm / 169.29".

Options

Options

Options

Options

Inputs / outputs

Current (incl. HART

®

), pulse, frequency and/or status output, limit

switch and/or control input (depending on the I/O version)

Counters

2 internal counters with a max. of 8 counter places (e.g. for counting

volume and/or mass units)

Self diagnostics

Integrated verification, diagnosis functions: flowmeter, process,

measured value, empty pipe detection, bargraph