B1-30 – Yokogawa YFGW710 User Manual
Page 94

B1-30
IM 01W01F01-01EN
l
Device tags do not match
When downloading the process data communication definitions to the device from Field Wire-
less Configurator and the device tag registered with the project database and the device tag set
to the device by provisioning do not match, the following message appears and the download is
stopped.
Device tag 1: Device tag registered with the project data base
Device tag 2: Device tag actually set to the device
In this case, either change the device tag in the project database, or perform the provisioning
task again and set the device tag to the field wireless device again. Note that when provisioning
is performed again, the provisioning information needs to be registered with the project database
and written to YFGW710 again.
l
CFs do not match
When the CF used by the field wireless network offline engineering does not match the CF of the
target device, a download error occurs.
Check whether or not the CF used is correct using the following procedure.
• In the [Download Project Data] window shown in Figure B1-7, place a check in the checkbox
for [Verify vendor and model before downloading device].
• Performing download
When a check is placed in the checkbox for [Verify vendor and model before downloading de-
vice], Field Wireless Configurator obtains the vendor ID and model ID in IDENT_NUMBER of
the device and compares them with the vendor ID and model ID in CF before downloading the
process data communication definitions. When the vendor IDs and model IDs do not match, the
following message appears and the download is stopped.
DeviceRev=1
Device tag: Device tag registered with the project database
Vendor ID: Device vendor (0x00594543 for Yokogawa)
Model ID: Device model (0x000C for EJX)
In this case, inform the device vendor about the vendor ID, model ID, and device revision, and
obtain CF that matches the device information. After obtaining CF, replace the existing CF with
a new CF using Field Wireless Configurator, and define the process data communication again.
Define the Modbus Register map again if necessary.
l
For the case that you find the following message when the timeout occurs
after starting the download without a marking “Verify vendor and model before
downloading to device” checkbox in the [Download Project Data] window:
DEV001 download failed due to EUI64 write ObjectAttributeIndexAndSize Array configured NG
due to timeout!! (Ex. Device TAG: DEV001)
When the above message appears during the download, wait for three minutes, and then per-
form the download to the target device again using Field Wireless Configurator.
l
For the case that you find the following message when the timeout occurs
after starting the download with a marking “Verify vendor and model before
downloading to device” checkbox in the [Download Project Data] window, de-
pending on the timing of the downloading of Field Wireless Configurator or the
timing of the device provisioning to the wireless network: