A3-37 – Yokogawa YFGW710 User Manual
Page 57

A3-37
IM 01W01F01-01EN
n
Optional Specifications(For Explosion Protected Types)
Item
Description
Code
Factory Mutual
(FM)
FM nonincendive approval
Applicable standard: FM3600, FM3611, FM3810, ANSI/NEMA250
Nonincendive for Class I, Division 2, Groups A, B, C and D;
Class II, Division 2, Groups F and G;
Class III, Division 1 hazardous (Classified) locations.
Enclosure: NEMA 4X
Temp. Class: T4, Amb. Temp.: –40 to 60°C (–40 to 140°F)
FN17
ATEX
ATEX Type n declaration
Applicable standard: EN60079-0: 2009, EN60079-0: 2012,
EN60079-11: 2012, EN60079-15: 2010, EN60079-28: 2007
II 3G Ex nA [ic] [op is] IIC T4 Gc (with 100BASE-FX)
II 3G Ex nA [ic] IIC T4 Gc (without 100BASE-FX)
Enclosure: IP66
Amb. Temp.: –40 to 60°C (–40 to 140°F)
KN27
Canadian Standards
Association
(CSA)
CSA nonincendive approval
Certificate: 2342292
[For CSA C22.2]
Applicable standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25,
C22.2 No.94, C22.2 No.213, C22.2 No.61010-1-04
Nonincendive for Class I, Division 2, Groups A, B, C and D;
Class II, Division 2, Groups F and G;
Class III, Division 1
Enclosure: Type 4X
[For CSA E60079]
Applicable standard: CAN/CSA E60079-0, CAN/CSA E60079-15,
IEC60529
Ex nA nL IIC T4
Enclosure: IP66
Amb. Temp.: –40 to 60°C (–40 to 140°F)
CN17
IECEx Scheme
IECEx Type n approval
Certificate: IECEx DEK 13.0047
Applicable standard: IEC60079-0:2011, IEC60079-15:2010,
IEC 60079-11:2011
Ex nA [ic] IIC T4 Gc
Enclosure: IP66
Amb. Temp.: –40 to 60°C (–40 to 140°F)
SN27