A3-25, Important, Nexplosion proof certifications caution – Yokogawa YFGW710 User Manual
Page 45

A3-25
IM 01W01F01-01EN
R&TTE:
ETSI EN 300 328, ETSI EN 301 489-17, EN61010-1, EN62311
FCC:
Part15.247
Contains FCC ID: SGJ-WFC001
IC:
RSS-210
Contains IC: 8999A-WIC001
IMPORTANT
• Microwave ovens and other industrial, scientific, and medical equipment, as well as local
wireless stations (license required) and specific low power wireless stations (license not
required) for identifying mobile objects used in the production line of a factory, use the same
frequency band as this product. Prevent interference with other wireless stations.
• Check that local wireless stations and specific low power wireless stations are not being
used in the vicinity before using this product.
• If this product causes radio interference in a local wireless station used for identifying mobile
objects, change the working frequency or stop the emission of radio waves immediately. For
details on how to prevent radio interference, contact our service office.
n
Explosion Proof Certifications
CAUTION
This instrument has been tested and certified as being explosion proof. Please note that severe
restrictions apply to this instrument’s construction, installation, external wiring, maintenance and
repair. A failure to abide by these restrictions could make the instrument a hazard to operate.
l
FM Approval
Caution for FM nonincendive. (Following contents refer to “DOC.NO. NFM023-A14 P.1 AND
P.2.”)
Note 1. Model YFGW710 Field Wireless Integrated Gateway with optional code /FN17 is
applicable for use in hazardous (Classified) locations.
• Applicable standard: FM3600, FM3611, FM3810, ANSI/NEMA 250
• Nonincendive for
Class I, Division 2, Groups A, B, C and D.
Class II, Division 2, Groups F and G.
Class III, Division 1
hazardous (Classified) locations.
• Enclosure: NEMA 4X (Indoors and outdoors).
• Temperature Class: T4
• Ambient Temperature: –40 to 60°C