<6. PARAMETER DESCRIPTION>

6-18

IM 01E30D01-01EN

[B30: Total Unit] Setting of units for totalization

scale

→ This setting is linked with that of parameter

D10.

This parameter selects the flow rate units for use in

totalization.

Item

Description

n Unit/P

10

-9

 FU

u Unit/P

10

-6

 FU

m Unit/P

10

-3

 FU

Unit/P

FU

k Unit/P

10

3

 FU

M Unit/P

10

6

 FU

Pulse/s

Number of pulses to be counted for one second

at 100% output.

FU: Flow rate unit selected in B21/C40: Base Flow Unit.

[B31: Total Scale] Setting of the totalization scale

→ This setting is linked with that of parameter

D11.

The flow rate is totalized in individual counts in

accordance with this parameter’s setting. If 0 is

selected, it indicates that the totalization function is

not to be used.

NOTE

If a totalization scale is specified upon ordering,

this parameter is set up before shipment;

however, if this is not the case, it will be

necessary for the appropriate value to be set up

by the user.

NOTE

• By setting the totalization scale, the

totalized value is displayed on the display

unit. The totalization scale is determined in

accordance with the settings of

B30/D10:

Total Unit and B31/D11: Total Scale.

• The maximum value that can be displayed is

99999999, and if this is exceeded, the value

0 is counted once again. However, counting

stops at 99999999 when the totalization

switch function is used.

• If multiple ranges are being used, the flow

rate span for the smallest range becomes

the standard for the

D13: Total Low Cut

setting value.

• Totalization for the reverse flow rate and for

the differential flow rate is carried out only

when “Fwd/Rev Ranges” is selected for

F10:

DO Function.

• The totalized units are indicated on the

display unit when

B31/D11 is 0.00001,

0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000,

or 10000. In the case of other setting values,

the totalized units are not indicated.

Example 1: To count in 1 Ml (mega-liter) steps

with flow rate span = 1000 m

3

/h

Since 1 Ml = 10

3

x m

3

, k Unit/P is set

for

B30/D10, and 1 is set for B31/

D11. “x10

3

m

3

” is indicated for the

totalized units in the Display Mode.

Example 2: To count in 10 l (liter) steps with flow

rate span = 100 m

3

/h

Since 1 l = 10

-3

x m

3

, m Unit/P is set

for

B30/D10, and 10 is set for B31/

D11. “x10

-2

m

3

” is indicated for the

totalized units in the Display Mode.

Example 3: To count in 5 l (liter) steps with flow

rate span = 100 m

3

/h

Since 1 l = 10

-3

x m

3

, m Unit/P is set

for

B30/D10, and 5 is set for B31/

D11. Since B31/D11 is not 0.00001,

0.0001, 0.001, 0.01, 0.1, 1, 10, 100,

1000, or 10000, there is no indication

of totalized units in the Display Mode.

• Setting of totalization scale is not possible

when specific selections have been made

for

B30/D10: Total Unit, B31/D11: Total

Scale, and B23/C42: Flow Span. In such

a case, a setting alarm will be displayed,

and parameters should be changed in

accordance with the instructions given.

[B32: Pulse Unit] Setting of the pulse units

This setting is linked with that of parameter

E10.

This parameter selects the flow rate units to be

used for pulse output.

Item

Description

n Unit/P

10

-9

 FU

u Unit/P

10

-6

 FU

m Unit/P

10

-3

 FU

Unit/P

FU

k Unit/P

10

3

 FU

M Unit/P

10

6

 FU

Pulse/s

Number of pulses to be output for one second at

100% output.

FU: Flow rate unit selected in B21/C40: Base Flow Unit.