<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-8
IM 01E30D01-01EN
a. Burst Command
Select the transmission data at
Burst Command
parameter.
Burst Command
Command parameter
Cmd1: PV
Variable assigned to PV
Cmd2: % range/current % range/current (Output in %
and Loop current)
Cmd3: Dyn vars/current Process vars/current
(Loop current, PV, SV, TV,
QV)
Cmd9: Device vars
w/Status
Process vars/% range/current
Mapping by user
Cmd48: Read
Additional Device
Status
Self diagnosis information
b. Burst Variable Code
This parameter need to be set when
Burst
Command is Cmd9:Device vars w/Status (up to
eight items).
• Procedure to call up the display
DD
DTM
[Root Menu] → Detailed setup →
Output condition →HART output →
Burst condition → Burst Message
1,2 or 3 → Burst Device Variables →
Burst Variable Code →
Display Item
Contents
PV
Instantanous flow rate
SV
Forward totalization value
TV
Reverse totalization value
QV
Differential totalization value
% rnge
% in output
Loop current
Current output
Not Used
–
c. Update period and Max Update Period
Set to
Update Period and Max Update Period.
When the period that is earlier than the operation
period of each process value was set, it is set
automatically to become bigger than an operation
period of the device.
For
Update Period, set the value that is smaller
than
Max Update Period.
• Procedure to call up the display
DD
DTM
[Root Menu] → Detailed setup →
HART output → Burst condition
→ Burst Message 1,2 or 3 → Set
Burst Period
→ Update Period
/ Max Update
Period
0.5 s
1 s
2 s
4 s
8 s
16 s
32 s
1 min
5 min
10 min
15 min
30 min
45 min
60 min
d. Burst Msg Trigger Mode
Set the
Burst Msg Trigger Mode from the
parameters shown below.
When
Burst Msg Trigger Mode is Window, Rising
or Falling, set the
Burst Trigger Level.
• Procedure to call up the display
DD
DTM
[Root Menu] → Detailed setup →
HART output → Burst condition →
Burst Message 1,2 or 3 → Set Burst
Trigger →
Display Item
Contents
Continuous
Burst Message is transmitted
continuously.
Window
In “Window” mode, the Trigger Value
must be a positive number and is the
symmetric window around the last
communicated value.
Rising
In “Rising” mode, the Burst Message
must be published when the source
value exceeds the threshold
established by the trigger value.
Falling
In “Falling” mode, the Burst Message
must be published when the source
value fall below the threshold
established by the trigger value.
On-change
In “On-change” mode, the Burst
Message must be published when the
source value on change established
by the trigger value.