<11. MAINTENANCE>

11-5

IM 01E30D01-01EN

11.3 Setting of Switches

11.3.1 Setting of Burnout Switch

The burnout function sets the direction of current

output in situations during occurring the system

alarm. Upon shipment from the manufacturing

plant, the burnout direction is set to High (21.6 mA

or more); however, in cases where the optional

code C1 has been specified, the output direction

will be set to Low (3.2 mA or less).
Modification of the burnout direction must be carried

out using the setting switch from the amplifier’s

board (Switch 2) (See Figure 11.3.1).

Table 10.3.1 Output Setting Pins for Burnout

Position of

Pin

Burnout

Direction

Burnout

Output

Remarks

L H

High

21.6 mA

or more

Set to High before

shipment

L H

Low

3.2 mA

or less

Set to Low for optional

code C1

NOTE

On the amplifier’s board, the burnout setting

switch (Switch 2) and the write protect switch

(Switch 1) are located adjacent to each other.

Accordingly, special care should be taken when

making switch settings.

Switch 2

Switch 1

Enable

Protect

L

H

1

2

ON

F1108.ai

BO ← Burnout setting switch

WR← Write protect setting switch

Figure 11.3.1 Switch Configuration

11.3.2 Setting of Write Protect Switch

By setting the write protect function to “Protect” it is

possible to prevent the overwriting of parameters.

Write protection can be carried out using either the

hardware switch on the amplifier board (Switch 1) or

software parameter settings. If either of these items

is set to “Protect,” the overwriting of parameters will

be prohibited.

NOTE

If the hardware switch is set to “Protect,” it

will not be possible to overwrite parameters;

furthermore, this condition will be maintained

until the switch is set to “Enable.”

For more details regarding usage of the write

protect function and the software’s parameter

switches, refer to “Chapter 6: Parameter

Description.”