<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>

8-2

IM 01E30D01-01EN

(2) Confirm the installed DD revision in

accordance with the procedure of the

Configuration Tool. Refer to its manual how

to confirm it in detail.

8.3 Interconnection between AXR and HART Configuration Tool

The HART Configuration Tool can interface with the AXR from the control room, the AXR site, or any other

wiring termination point in the loop, provided there is a minimum load resistance of 250 Ω between the

connection and the receiving instrument. To communicate, it must be connected in parallel with the AXR, and

the connections must be non-polarized. Figure 8.3.1 illustrates the wiring connections for a direct interface at

the AXR site. The HART Configuration Tool can be used for remote access from any terminal strip as well.

AXR

F0802.ai

+

SUPPLY

DO

USB

FieldMate

modem

Relaying

terminals

Distributor

Control room

Terminal

board

USB

PC/FieldMate

Figure 8.3.1 Connecting the HART Communicator

WARNING

Be sure to set parameters as “Protect” on the

write protect function after finish of parameter

setting work.

Refer to “Chapter 6 Menu P: Parameter

Protection items” and section “11.3.2” how to use

the write protect function in detail.

IMPORTANT

If the power of flowmeter is turned off within 30

seconds after parameters have been set, these

settings will be canceled. Accordingly, please

keep the power on for at least 30 seconds after

setting parameters.

NOTE

Before updating any setting, remember to

always check the parameter content you want

to change as described in Chapter 6: Parameter

Description.

NOTE

In case of HART Configuration, the parameters

are displayed in English only.

Even if the language with the exception of

English is selected at “Language” setting display,

the parameters are displayed in English upon

HART Configuration Tool.

8.2.2 Device Type Manager (DTM) and

Device Revision

When configure the parameters using FieldMate,

use the DTM (Device Type Manager) referring to

the following table.

MODEL

DTM

Name

Device

Type

Device

Revision

AXR

AXR V2.1

AXR (0x57)

2

The device revision can be checked as follows.

DTM

Configuration → HART → Fld dev

rev