beautypg.com

7 ups enable/disable, 8 ups/battery mode selection, Table 5-8: ups enable/disable jumper settings – IEI Integration eKINO-945GSE v1.01 User Manual

Page 90

background image

eKINO-945GSE Motherboard

Page 74

5.7.7 UPS Enable/Disable

Jumper Label:

JP3

Jumper Type:

2-pin header

Jumper Settings:

See Table 5-8

Jumper Location:

See Figure 5-4

When this jumper is closed, the system will use the battery when needed, when open the

system will not use the battery.

Pin Setting

Description

Open

Don't use the battery backup

Closed

Use the battery function

Table 5-8: UPS Enable/Disable Jumper Settings

5.7.8 UPS/Battery Mode Selection

Jumper Label:

J_U/B1

Jumper Type:

3-pin header

Jumper Settings:

See Table 5-9

Jumper Location:

See Figure 5-4

This jumper sets the system to run off the battery exclusively, or to use the battery as a

UPS.

Pin Setting

Description

1-2

UPS

2-3

Battery

Table 5-9: UPS/Battery Mode Selection Jumper Settings