Micromod MOD: MODCELL Application Builder Software User Manual
Page 77
Application Builder
CONFIGURATION
TOT
Totalizer Block. Reference IB-23G602 Section 8.10. This block is used
to count an analog input signal. Features include: Threshold, Up, Down,
Wrap, Scale Factor, Predetermined Count 1 & 2 and Limit Status.
5.5.5 Sequencer Block Selection
Sequencer blocks can only be placed in a loop compound. The sequencer
blocks support batch control for the instrument. There are three types of
sequencer blocks, all providing the same batch control functions. They differ
only in their input, output, and step capacities. Reference IB-23G602.
Sequencer Block Types:
DVC
Device Block. This block provides for 6 inputs, 4 outputs, and 10
steps.
SSEQ Small Sequencer Block. This block provides for 30 inputs, 15 outputs,
and 20 steps.
LSEQ Large Sequencer Block. This block provides for 100 inputs, 30
outputs, and 80 steps
5.5.6 Advanced Algorithm Block Selection
Advanced algorithm blocks can only be placed in a loop compound. The types
are:
PID
Regulatory Control Block (Proportional, Integral, Derivative). Reference
IB-23G601 Section 2. This block supports regulatory control for the
instrument.
RSK
Ramp/Soak Profile Block. Reference IB-23G601 Section 3. This block
supports up to 36 ramp or soak segments. Functions supported
include: Repeat, Tracking, Guaranteed ramps or soaks, four segment
event states, Reset, Stop, Run, Hold and Skip. This block is typically
used as a remote setpoint input to a PID block.
5-13