beautypg.com

Micromod MOD: MODCELL Application Builder Software User Manual

Page 29

background image

Application Builder

USER BASICS

3.11

INPUT CONVENTIONS

Several conventions are used throughout the edit block displays. Typically:

• "Gray" data is viewable only.

• Data with a checkbox next to it is dynamic.

To enter data, click on the checkbox. This will enable the associated data
field(s) for user entry. To disable, click on the checkbox again.

• Other data may be dynamic, that is, enabled by entries from other fields.

• Data entry fields are either "Keyed" (data is entered through the keyboard),

or "Scrolled" (data is selected by scrolling through a list with the mouse).

Most blocks allow one or more inputs. An input can be:

• A remote input. This is a connection arrow from some other block.

• A local input. This is data entered directly in the block menu.

• NONE (no input). No remote input and no local input.

Most inputs can be remote, local, or NONE:

• Specify a remote input by making a connection to the appropriate block

attribute.

• Specify a local input by enabling the checkbox in the block menu and

entering local data.

• Specify NONE by making no connection and disabling the checkbox in the

block menu.

Some inputs can be remote only:

• Specify a remote input by making a connection to the appropriate block

attribute.

• There's no checkbox or local data field in the block menu.

Some inputs can be remote or local, but not NONE:

• Specify a remote input by making a connection to the appropriate block

attribute.

• Specify a local input by entering local data in the block menu.

• There's no checkbox to disable for indicating NONE.

3-13