Application builder – Micromod MOD: MODCELL Application Builder Software User Manual
Page 71
Application Builder
CONFIGURATION
5.4.2 Example of Defining Parameters for ICN Module Block
Double click on the block icon to open the block edit display. Edit any fields
that require new values. Section 3.6 describes edit block displays. Bypass
any field whose default value is appropriate for the application at hand (if ICN
module location is set correctly, the defaults will allow ICN comunication).
Move between pages of a multiple page display as required.
For example, select ICN from the Communication library display, place it and
open it to the edit block display for the ICN Communication block as shown in
Figure 5-3. Use the planning forms to organize parameter entry. Refer to the
data base reference book for detailed descriptions of the data base parameters.
Figure 5-3
.
Example, ICN Communication (ICN), Block Edit Display, Page 1
Inst Type:
All Devices
SLU
=
Sequence and Logic Unit
PC30
=
PC-30 Software
MOD 300
1180M
=
Accuray 1180M
MODCELL
ICN Addr:
ICN address switch setting for
ICN interface board (board that
the instrument ICN is
connected to). The range of
valid addresses is 0-15.
Enable/Disable:
ANY = Any authorized source
(Source 1 only,
remaining entries
ignored)
One parameter of particular importance is the Authorized Computer Sources
parameter. This parameter is used to establish control devices for the
instrument being configured. For example, entering PC30 as the device type
allows an operator to control the instrument through the PC-30 runtime displays.
5-7