beautypg.com

Dynasonics TFX Ultra Transit Time Flow Meters User Manual

Page 78

background image

Protocol Implementation Conformance Statement (Normative)

BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

Date:

03/22/2011

Vendor Name:

Racine Federated Inc

Product Name:

TFX Ultra Flow meter

Product Model Number:

TFX

Application Software Version:

1.08

Firmware Revision:

N/A

BACnet Protocol Revision:

4

Product Description:

Clamp-on ultrasonic flow and energy meters for liquids

BACnet Standardized Device Profile (Annex L):

…

BACnet Operator Workstation (B-OWS)

…

BACnet Building Controller (B-BC)

…

BACnet Advanced Application Controller (B-AAC)

„

BACnet Application Specific Controller (B-ASC)

…

BACnet Smart Sensor (B-SS)

…

BACnet Smart Actuator (B-SA)

List all BACnet Interoperability Building Blocks Supported (Annex K):

y

Data Sharing-ReadProperty-B (DS-RP-B)

y

Data Sharing-WriteProperty-B (DS-WP-B)

y

Data Sharing - ReadProperty Multiple - B (DS-RPM-B)

y

Data Sharing - WriteProperty Multiple - B (DS-WPM-B)

y

Device Management-Dynamic Device Binding-B (DM-DDB-B)

y

Device Management-Dynamic Object Binding-B (DM-DOB-B)

y

Device Management-DeviceCommunicationControl-B (DM-DCC-B)

Segmentation Capability:

…

Segmented requests supported

Window Size

…

Segmented responses supported

Window Size

Standard Object Types Supported:

y

Device Object

y

Analog Input Object

y

Binary Output Object

BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

Page 78

March 2014