BACnet® Object Support
Nine BACnet standard objects are supported, a Device object (DEx), a Binary Output object (BO1), and seven Analog Input
objects (AI1 through AI7). The BACnet/IP UDP port defaults to 0xBAC0. The Object Identifier (BACnet Device ID) and Location
can both be modified through the web page interface.
DEx
Object_Identifier
Defaults to DEx
Can modify “x” through web page (1-9999)
W
Object_Name
Up to 32 characters
W
Object_Type
DEVICE (8)
R
System_Status
OPERATIONAL or NON_OPERATIONAL
R
Vendor_Name
“Racine Federated Inc.”
R
Vendor_Identifier
306
R
Model_Name
“D(X)TFX”
R
Application_Software_Version
“1.07”
R
Location
“Sample Device Location”
Up to 64 characters - can modify through web page
W
Protocol_Version
1
R
Protocol_Revision
2
R
Protocol_Services_Supported
{ readProperty, writeProperty, readPropertyMultiple,
writePropertyMultiple, deviceCommunicationControl, who-Has,
who-Is }
R
Protocol_Object_Types_Supported
{ AnalogInput, BinaryOutput, Device }
R
Object_List
DEx, AI1, AI2, AI3, AI4, AI5, AI6, AI7, BO1
R
Max_APDU_Length_Accepted
1476
R
Segmentation_Supported
3 – NONE
R
APDU_Timeout
3000 default
R
Number_Of_APDU_Retries
1 default
R
Device_Address_Binding
always empty
R
Database_Revision
0
R
Table 18: BACnet standard objects