Channel 2 – Control Output Configuration Flow Only

Two independent open collector transistor outputs are included with the flow only model. Each output can be configured

independently to alarm for one of the following. See

ALARM OUTPUTS

for output details.

None
Batch / Total
Flow
Signal Strength
Errors

Do w n l o a d

Ca n c el

F i l e Op en . . .

F i l e Sa v e. . .

S y s t e m C o n f i g u r a t i o n

Display

Basic Flow Filtering Output Security

Co n tr o l Ou tp u ts

Channel 2:

50

Off <

Gal/M

350

On>

Gal/M

Mode:

F l o w

Control 1

50

Off <

Gal/M

350

On>

Gal/M

Mode:

F l o w

Mode:

No n e

Control 2

4-20m A / F r eq u en c y

Channel 1:

0

Flow at 4mA / 0Hz:

Gal/M

400

Flow at 20mA / 1KHz:

Gal/M

Calibration/Test

Test

Calibration

4 m A

20 m A

32

3837

Test

4

F l o w

B a tc h / To ta l
F l o w
Si g Str en g th
E r r o r s

Co n tr o l Ou tp u ts

Channel 2:

Figure 45: Channel 2 output choices

OTE:

N

The Batch/Total output is limited to 1Hz maximum pulse rate.

None

All alarm outputs are disabled.

Batch / Total

Multiplier (Value)

This is the value to which the totalizer will accumulate before resetting to zero and repeating the accumulation. This value

includes any exponents that were entered in the BASIC menu as TOTAL E. See

ALARM OUTPUTS

.

50

Multiplier

Mode:

B a tc h / To ta l

Control 1

Figure 46: Control output set for batching

BASIC TAB

Page 63

March 2014