Low Flow Cut-off

FL C-OFF — Low Flow Cut-off (Value)

0…100%

A low flow cut-off entry is provided to allow very low flow rates (that can be present when pumps are off and valves are

closed) to be displayed as zero flow. Typical values that should be entered are between 1.0% and 5.0% of the flow range

between MIN RATE and MAX RATE.
Damping Percentage

DAMP PER — System Damping (Value)

0…100%

Flow filter damping establishes a maximum adaptive filter value. Under stable flow conditions (flow varies less than 10%

of reading), this adaptive filter will increase the number of successive flow readings that are averaged together up to this

maximum value. If flow changes outside of the 10% window, the flow filter adapts by decreasing the number of averaged

readings which allows the meter to react faster. Increasing this value tends to provide smoother steady-state flow readings

and outputs. If very erratic flow conditions are present or expected, other filters are available for use in the software utility. See

SOFTWARE UTILITY

of this manual for further information.

CH1 Menu — Channel 1 Menu

CH1 MENU — 4-20 mA Output Menu

4-20 MA — 4-20 mA Setup Options (Values)

FL 4MA

Flow at 4 mA

FL 20MA

Flow at 20 mA

CAL 4MA

4 mA Calibration

CAL 20MA

20 mA Calibration

4-20 TST

4-20 mA Test

The CH1 menu controls how the 4-20 mA output is spanned for all flow meter models and how the frequency output is

spanned for the flow only model.
The FL 4MA and FL 20MA settings are used to set the span for both the 4-20 mA output and the 0…1000 Hz frequency output

on the flow only meter versions.
The 4-20 mA output is internally powered (current sourcing) and can span negative to positive flow/energy rates. This output

interfaces with virtually all recording and logging systems by transmitting an analog current that is proportional to system

flow rate. Independent 4 mA and 20 mA span settings are established in firmware using the flow measuring range entries.

These entries can be set anywhere in the –40…40 fps (–12…12 mps) range of the instrument. Resolution of the output is

12-bits (4096 discrete points) and the can drive up to a 400 Ohm load when the meter is AC powered. When powered by a DC

supply, the load is limited by the input voltage supplied to the instrument. See

Figure 23

for allowable loop loads.

FL 4MA — Flow at 4 mA
FL 20MA — Flow at 20 mA

The FL 4MA and FL 20MA entries are used to set the span of the 4-20 mA analog output and the frequency output on flow only

versions. These entries are volumetric rate units that are equal to the volumetric units configured as RATE UNT and RATE INT

discussed previousley.
For example, to span the 4-20 mA output from –100…100 gpm, with 12 mA being 0 gpm, set the FL 4MA and FL 20MA inputs

as follows:

FL 4MA

= –100.0

FL 20MA

= 100.0

If the meter were a flow only model, this setting would also set the span for the frequency output. At –100 gpm, the output

frequency would be 0 Hz. At the maximum flow of 100 gpm, the output frequency would be 1000 Hz, and in this instance a

flow of zero would be represented by an output frequency of 500 Hz.

BSC MENU – BASIC MENU