beautypg.com

Dynasonics TFX Ultra Transit Time Flow Meters User Manual

Page 74

background image

Object Description

BACnet Object

(Access Point)

Notes

Available Units

Signal Strength

AI1

Analog Input 1

Flow Rate

(Flow model)

Energy Rate

(BTU model)

AI2

Analog Input 2

Gallons, Liters, MGallons,

Cubic Feet, Cubic Meters,

Acre Feet, Oil Barrel, Liquid

Barrel, Feet, Meters, Lb, Kg,

BTU, MBTU, MMBTU, TON, kJ,

kW, MW
Per Second, Minute, Hour,

Day

Net Totalizer

AI3

Analog Input 3

Positive Totalizer

AI4

Analog Input 4

Negative Totalizer

AI5

Analog Input 5

Temperature 1

AI6

Analog Input 6

° C

Temperature 2

AI7

Analog Input 7

° C

Reset Totalizers

BO1

Binary Output 1

Writing an (1) active state to this object

will reset all totalizers. The Object will

then automatically return to the (0)

inactive state.

Table 17: Flow meter BACnet object mappings