4§parameters§settings, 5§controller§concept, Page 75 k5 system technical guide – V-Tech CAT5 System Technical Guide User Manual
Page 75

Page 75
K5 System Technical Guide
4.4.2.4§Parameters§Settings
All the parameters of C5-IPC can be set through IP-Device. See IP-Device manual for detail.
4.4.2.5§Controller§Concept
Controller in the system serves as the controlling center, it controls data communicating, audio
and video distribution. Of all the devices, Door station and C5-IPC can be set to be the controller.
Rules must be followed as below:
1) There must be one and only one controller in the system.
2) C5-IPC is designed to be the controller by default, and cannot be set to be non-controller
3) Door station must be set to be non-controller when working with C5-IPC.
How to set Controller on door station:
V i d e o E n t r y S y s t e m
- - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - -
> > D E B U G S T A T E < <
- - - - - - - - - - - - - - - - - - - - - - - - - - -
3 - # M o n i t o r P r o g r a m
2 - # S e t u p
1 - # I n s t a l l e r S e t u p
6 - # O n l i n e D e v i c e s . . .
E X I T: # - 9 0 0 9
5 - # O n l i n e M o n i t o r. . .
- - - - - - - - - - - -To o l s - - - - - - - - - -
4 - # C a r d M a n a g e
V i d e o E n t r y S y s t e m
* B a c k
P r e s s 1 ~ 9 t o s e l e c t
- - - - - - - - - - - - - - - - - - - - - - - - - - -
8. I n s t a l l e r C o d e
7. P a r a m e t e r s . . .
6. A u d i o O p t i o n . . .
5. D o o r p l a t e M o d e . . .
4. C a r d M e m o r y
3. U n l o c k O u t p u t
2. U n l o c k T i m i n g
[ 1] I n s t a l l e r S e t u p
1. D S S e r i a l N O .
- - - - - - - - - - - - - - - - - - - - - - - - - - -
9. D e f a u l t. . .
V i d e o E n t r y S y s t e m
. . [ 1 ] [ 1 ]
* B a c k # S a v e
( 0~ 9 )
[ - ]
D S S e r i a l N O .
0: 1D S S t a n d a l o n e
1~ 8 : M u l t i D S N O.
9: C o m m o n D o o r S t a t i o n
In standby mode, in-
put #9008+password
(66666666, by default)
On the keypad, input 1 to
enter DS Serial NO.
Input the number according
to the information, then # to
save the parameter
Notes:
1. DS Serial NO. set to be 0, the door station serves as the controller
2. DS Serial set to be from 1~8 to be non-controller, if there is no C5-MDS(only one
door station), the door station must be set to 1
3. DS Serial NO. set to 9 to work as common door station