6.3
Detector test
1.
Switch the FAD-420-HS-EN to test mode on the fire panel.
2.
If you have activated the jumper for the tamper switch,
secure a magnet at the reed switch (E) on the side of the
detector housing.
You could use IMI-ESMAG (F.01U.142.997) magnets, for
example.
3.
This bridges the tamper switch (F) and allows the cover
(B) to be removed without having to switch off the FAD-
O420 Smoke Detector (D).
4.
Loosen the fastening screws (A) on the cover and remove
the cover (B).
5.
Check both air filters (C) for contamination and replace
them if necessary.
If necessary, check and clean the sample tube and
ventilation tube.
6.
Test the FAD-O420 Smoke Detector (D) with a suitable
test aerosol.
7.
Once the detector is checked, reattach the cover, remove
the magnets, and set the detector to operating mode on
the fire panel.
- LBB 1961 (16 pages)
- DSDA ISCSI DISK ARRAY SERIES DSA-N2B20 (40 pages)
- MIC400 (20 pages)
- 2000 (72 pages)
- 3455 12V (2 pages)
- VMD01 M50 PAL (122 pages)
- RF835E (2 pages)
- D1260 (100 pages)
- DS422I (4 pages)
- D296/D297 (12 pages)
- 8-Dec (506 pages)
- MX938I (4 pages)
- FAS-420-TM-RVB (98 pages)
- FSM-2000 (40 pages)
- D720 (32 pages)
- FMM-7045 Series (2 pages)
- LTC 2210 (12 pages)
- FLM-420-RLV1 Relay Interface Modules Low Voltage (24 pages)
- FLM-320-EOL4W-S Conventional EOL Module 4-Wire (24 pages)
- FPE-5000-UGM Interface Module (32 pages)
- IOS 0020 A 20 mA Communication Module (32 pages)
- FLM-420-RLE-S Extinguishing Interface Module (28 pages)
- FCS-320-TM Series Conventional Aspirating Smoke Detectors (76 pages)
- LBC3474 (1 page)
- FLM-420 (32 pages)
- NZM 0002 A Notification Appliance Zone Module (24 pages)
- FLM-420-RHV Relay High Voltage Interface Modules (44 pages)
- FLM-I 420-S Short Circuit Isolator (36 pages)
- FPP-5000 External Power Supply Unit Kit 24 V (60 pages)
- FPP-5000 External Power Supply Unit Kit 24 V (28 pages)
- FNM-420-A-BS Base Sounder, Indoor (6 pages)
- FMC-420RW Single Action Call Points LSN improved (28 pages)
- BAT 100 LSN Display Panel (16 pages)
- LBC3473 (2 pages)
- FLM-420-O8I2-S Octo-output Interface Module with 2 Inputs (40 pages)
- FLM-420-RLV8-S Octo-relay Interface Module Low Voltage (24 pages)
- IOP 0008 A Input (32 pages)
- FAS-420-TM Series Aspirating Smoke Detectors LSN improved version (96 pages)
- RMH 0002 A Relay Module (24 pages)
- FNM-320 Sounders Conventional (20 pages)
- IOS 0232 A RS232 Communication Module (32 pages)
- ANI 0016 A Annunciator Module (32 pages)
- THP 2020 A Thermal Printer (32 pages)
- RML 0008 A Relay Module (32 pages)