beautypg.com

Bosch FAD-420-HS-EN Duct Smoke Detector User Manual

Page 61

background image

Duct Smoke Detector

Installation | en

61

Bosch Sicherheitssysteme GmbH

Installation guide

F.01U.033.733 | 5.0 | 2011.11

8.

Place the foam rubber sealing rings on the back of the FAD-

420-HS-EN on the mounting flanges of the sample tube and

ventilation tube (see Figure 4.7).

9.

Mount the FAD-420-HS-EN on the ventilation duct and use

the #10-24 x 1 in. screws to secure onto the expanding

nuts (see Figure 4.8).

Do not over-tighten the screws. Over-tightening the screws

can cause the ventilation duct sheet to buckle!

10. Remove the ventilation tube and sample tube from the

box. Check whether the end plug is inserted into the

sample tube (see Figure 4.9).

Figure 4.7

Foam rubber sealing rings

No.

Description

e

Ventilation tube mounting

flange

f

Ventilation tube mounting

flange

g

Foam rubber sealing rings

Figure 4.8

Housing installation

No.

Description

h

Ventilation duct

i

Detector housing

k

#10-24 x 1 in. screws

Figure 4.9

Sample tube and ventilation

tube

No.

Description

l

Ventilation tube

m

The ventilation tube must be

open at both ends!

n

Sample tube

o

The end plug must be

inserted!