en | Installation

Duct Smoke Detector

F.01U.033.733 | 5.0 | 2011.11

Installation guide

Bosch Sicherheitssysteme GmbH

11. The direction of the airflow must be taken into account

when installing the sample tube! The extraction holes must

face into the airflow (see Figure 4.10).

12. If the detector was installed according to position 2 of

Figure 3.2, then the ventilation tube should be positioned

downstream of the sample tube (see Figure 4.11).

13. Insert the sample tube and ventilation tube through the

securing flanges and ensure that the locating pins align

with the designated indents. The extraction holes on the

sample tube must face into the airflow! Fit both securing

flanges and mount with the four #8-32 x 9/16 in. screws.

Tighten the screws by hand.

14. Place the air filters on the ends of the sample tube and

ventilation tube (see Figure 4.13).

15. Now visually check the complete installation.

Figure 4.10

Airflow direction

No.

Description

p

Airflow direction

r

Sample tube

s

Extraction holes

Figure 4.11

Position of sample tube and

ventilation tube

No.

Description

p

Airflow direction

r

Sample tube

t

Ventilation tube

Figure 4.12

Installing the securing flanges

No.

Description

r

Sample tube

t

Ventilation tube

u

Securing flanges