en | Configuration

Duct Smoke Detector

F.01U.033.733 | 5.0 | 2011.11

Installation guide

Bosch Sicherheitssysteme GmbH

6

Configuration

6.1

Jumper setting

* Default setting

6.2

Checking the airflow

Optional:

To ensure that the system is functioning correctly, check that

the air speed enables a sufficient differential pressure to be set

in the device. This can be done by using a manometer. The air

speed in the duct should read between 1.5 m/s and 20 m/s.

The differential pressure between the sample tubes must

measure within the following range:

FAD-420-HS-EN Connection Board
No.

Configuration

2-3

Tamper switch deactivated*

1-2

Tamper switch activated

FAD-RB-DIBT Relay Board
No.

Configuration

1-2

Relay drops out if there is no

power and/or the detector C

point is activated.

2-3

Relay switches on if the

detector C point is

activated.

NOTICE!

Adjust the sensitivity of the detector by using the programming

software on the control panel.

Please refer to the software's online help.

Minimum

Maximum

0.25 mm H

2

O (0.01 in. H

2

O)

4.57 cm H

2

O (1.8 in. H

2

O)

0.025 mbar

4.48 mbar

2.5 Pa

448 Pa