en | Installation/configuration notes
Duct Smoke Detector
F.01U.033.733 | 5.0 | 2011.11
Installation guide
Bosch Sicherheitssysteme GmbH
3
Installation/configuration notes
3.1
Prerequisite
The FAD-420-HS-EN Duct Smoke Detector is designed for use in
ventilation systems with air speeds from 1.5 m/s to 20 m/s.
Check the ventilation system specifications before installation
to ensure these limits are adhered to.
F
Reed switch for bridging the tamper switch (x)
G
Sample tube
H
Ventilation tube
I
3-pole connector plug
J
2-pole connector plug
K
#8-32 x 9/16 in. screws for mounting the securing flanges (L)
L
Securing flanges for sample tube and ventilation tube
M
#10-24 expanding nuts for installing housing on ventilation duct
N
#10-24 x 1 in. screws for installing housing on ventilation duct
O
Air filters for sample tube and ventilation tube
P
Foam rubber sealing rings
x
Tamper switch for monitoring unauthorized opening of the cover
Pos. Description
Figure 3.1
Typical installation position
No.
Description
a
Bend or other delay to the
airflow
b
At least 3 x d
c
Turbulence through the
bend (a)
d
Width of the ventilation duct