Configuring Networks

3-28

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

Checking and Adapting the Slot Time

To allow a “bumpless” return from the optical bus to the optical ring after the fault
has been eliminated, there must be no frame on the network at the switch-back
time. The network is briefly free of frames when a master addresses a device
whose address is configured but does not actually exist.

The master waits for a response until the configured slot time has elapsed. The
OLM recognizes this frame–free state and closes the optical bus in the middle of
this query sequence to form the optical ring again.

The slot time must be set to approximately twice the value you would use in a
non-redundant network.

Calculate the slot time according to the following formula:

Slot time = a + (b x length

FOC

) + (c x number

OLM

)

Slot time

is the monitoring time in bit times

Length

FOC

is the sum of all FO cables (segment lengths) in the network.
The lengths must be specified in km.

Number

OLM

is the number of PROFIBUS OLMs in the network

The factors a, b and c depend on the transmission rate and can be found in Tables
3–9 and 3–10.