Active Components for RS-485 Networks

5-13

PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000

5.5

Connecting the Power Supply

Cable Type

To connect the 24 V power supply, use flexible cables with a cross section of 0.25
mm

2

to 2.5 mm

2

(AWG 26 to 14).

Connecting the Power Supply

To connect the power supply of the RS-485 repeater:

1. Strip the insulation from the wire for the 24 V DC power supply.

2. Connect the cable to terminals “L+”, ”M” and “PE”.