Configuration
6.2 Configuration of redundant optical rings
Data rate
a
b
c
12
MBit/s
1)
1651
240
28
6
MBit/s
1)
951
120
24
3
MBit/s
1)
551
60
24
1.5 MBit/s
351
30
24
500
kBit/s
251
10
24
187.5 kBit/s
171
3.75
24
93.75 kBit/s
171
1.875
24
45.45 kBit/s
851
0.909
24
19.2 kBit/s
171
0.384
24
9.6
kBit/s
171
0.192
24
Table 3a: Constants for calculating the slot time at DP standard
(redundant optical ring)
Data rate
a
b
c
12
MBit/s
1)
1651
240
28
6
MBit/s
1)
951
120
24
3
MBit/s
1)
551
60
24
1.5 MBit/s
2011
30
24
500
kBit/s
771
10
24
187.5 kBit/s
771
3.75
24
93.75 kBit/s
451
1.875
24
45.45 kBit/s
851
0.909
24
19.2 kBit/s
181
0.384
24
9.6 kBit/s
171
0.192
24
Table 3b: Constants for calculating the slot time at DP/FMS (”universal“)
and DP with S5 95U (redundant optical ring)
The calculation of the slot time only takes into consideration the optical network and the connection of bus sub-
scribers to the OLM via an RS 485 bus segment with a respctive length of max. 20 m. Longer RS 485 bus segments
must be allowed for by adding them to the Length
OF
.
Note:
When the slot time is configured with a too small value the OLM will, through it’s fault function and fault indications,
indicate such. The System-LED will blink red/green.
1)
Using the OLM/G11-1300 and OLM/G12-1300 at data rates of 12 MBit/s, 6 MBit/s, 3 MBit/s and 1.5 MBit/s the
minimum slot times according to the following table must be met.
Data rate
Minimum slot time
12 MBit/s
3800 t
Bit
6 MBit/s
2000 t
Bit
3 MBit/s
1000 t
Bit
1.5 MBit/s
530 t
Bit
Table 4: Minimum slot time on OLM/G11-1300 and
OLM/G12-1300
Use the values from Table 4 if the calculated slot time is smaller than the minimum slot time indicated in the table.