beautypg.com

Siemens SIMATIC NET PROFIBUS User Manual

Page 426

background image

30

Version 1.0 8/00

Configuration

6.2 Configuration of redundant optical rings

Data rate

a

b

c

12

MBit/s

1)

1651

240

28

6

MBit/s

1)

951

120

24

3

MBit/s

1)

551

60

24

1.5 MBit/s

351

30

24

500

kBit/s

251

10

24

187.5 kBit/s

171

3.75

24

93.75 kBit/s

171

1.875

24

45.45 kBit/s

851

0.909

24

19.2 kBit/s

171

0.384

24

9.6

kBit/s

171

0.192

24

Table 3a: Constants for calculating the slot time at DP standard
(redundant optical ring)

Data rate

a

b

c

12

MBit/s

1)

1651

240

28

6

MBit/s

1)

951

120

24

3

MBit/s

1)

551

60

24

1.5 MBit/s

2011

30

24

500

kBit/s

771

10

24

187.5 kBit/s

771

3.75

24

93.75 kBit/s

451

1.875

24

45.45 kBit/s

851

0.909

24

19.2 kBit/s

181

0.384

24

9.6 kBit/s

171

0.192

24

Table 3b: Constants for calculating the slot time at DP/FMS (”universal“)

and DP with S5 95U (redundant optical ring)

The calculation of the slot time only takes into consideration the optical network and the connection of bus sub-
scribers to the OLM via an RS 485 bus segment with a respctive length of max. 20 m. Longer RS 485 bus segments
must be allowed for by adding them to the Length

OF

.

Note:
When the slot time is configured with a too small value the OLM will, through it’s fault function and fault indications,
indicate such. The System-LED will blink red/green.

1)

Using the OLM/G11-1300 and OLM/G12-1300 at data rates of 12 MBit/s, 6 MBit/s, 3 MBit/s and 1.5 MBit/s the
minimum slot times according to the following table must be met.

Data rate

Minimum slot time

12 MBit/s

3800 t

Bit

6 MBit/s

2000 t

Bit

3 MBit/s

1000 t

Bit

1.5 MBit/s

530 t

Bit

Table 4: Minimum slot time on OLM/G11-1300 and

OLM/G12-1300

Use the values from Table 4 if the calculated slot time is smaller than the minimum slot time indicated in the table.